Errors of the Modbus communication
Data transmission
between the
Modbus master
and measuring
transmitter
interrupted
The PLC does not
receive any
plausible input
data
Cause
Remedy
– Wrong wiring
– Check / change the connections
– Wrong setting of the address,
baud rate, parity
– Check / change the settings
– Incorrect protocol
– Adjust the protocol
– Measuring transmitter defec-
tive
– Contact the service department
Cause
Remedy
– The data interpretation is
incorrect
– Observe the data formats of the mea-
suring transmitter
– The data interpretation of the
PLC is incorrect
– Observe the data alignment of the PLC
data representation. If necessary,
exchange the most significant and least
significant bytes word by word