![WTI IPS-15 Скачать руководство пользователя страница 37](http://html1.mh-extra.com/html/wti/ips-15/ips-15_user-manual_1000472037.webp)
Web Browser Interface:
Click the "Setup" button to access the
configuration menus, and then click the Web Server Parameters
button. The Web Server Parameters Menu will be displayed as
shown in Figure 5.12.
Text Interface:
Type
/W
and press
[Enter]
. The Web Server
Parameters Menu will be displayed as shown in Figure 5.13.
The Web Server Parameters Menu allows the following parameters
to be defined. Please note that all parameters listed here are
available via both the Web Browser Interface and the Text Interface.
·
Service:
Enables/Disables the IPS's Web Server. Note that when
the Web Server is disabled, you will not be able to communicate
via the Web Browser Interface. (Default = On.)
·
Port Number:
Sets the TCP/IP Port Number. The Port Number
can be set to any valid number except 23; this is because 23 is the
default port number that is used for communication with the unit
via Telnet. (Default = 80.)
5-15
Section 5: Configuration
Figure 5.12: Web Browser Parameters Menu - Web Browser Interface
WEB SERVER:
1. Service:
On
2. Server Port #:
80
Enter Selection or <ESC> to Exit ...
Figure 5.13: Web Browser Parameters Menu - Text Interface