MReX-MB1 Transmitter User Manual v3.16 Firmware
Configuration
Parameters can be changed using any common serial terminal program. A free serial terminal
program that also allows saving and loading of configuration files can be downloaded from
Start-up operation is always at 9600:8-N-1.
The MReX-MB1 integrates the MReX-460 module, therefore has available the MReX-460
command set. However, only a subset of those commands are relevant to the MReX-MB1.
Relevant commands are listed below.
All configuration commands always start with the asterisk ‘*’ character.
All messages that do not start with the * character are processed by the protocol decoder.
All messages are terminated by a Carriage Return character, shown in this manual as <CR>
All commands that accept a value, can have that value read back by using the ‘?’ suffix. E.g.
*TX_FREQ?
Returns
*TX_FREQ=460000000
(for example)
Note:
It is a good practice to restart the unit after changing configuration. This can be achieved by
removing the coin cell.
© WTE Limited, 2021 – Christchurch New Zealand
Page 10 of 34