Original Operating Instructions
BATI0XXX-ES-1-ZZZ-1
Installation
O_BATI_0XXX-ES-1-ZZZ-1_V1.4_GB
Seite
36
von
60
3.4.5 Option Island Grid Function
This function is only available if the option island grid function is purchased. In delivery
state the function is activated. To change to the grid feeding modus a supply voltage of
+24V
DC
on terminal (-X2.9-10) is necessary. If the terminal (-X2.9-10) is not supplied
the island grid function is activated.
Island grid function inactivated:
1.
Remove
the sliding ground plate.
2.
Find
terminal strip (-X2) in the control cabinet (Figure 6).
3.
Apply
a voltage of +24 VDC to terminal (
–X2.9-10) (Figure 16).
Figure 16: Voltage detection for island grid function or grid feeding
3.4.6 Customer Feedback AC Circuit Breaker (Optional)
The switching states of the AC circuit breaker (
–Q2) can be queried via terminal (–X2)
located in the control cabinet.
Figure 17: Customer feedback AC circuit breakers
Switching state
Terminal
Contact
Circuit breaker
switched off
(-X2.11) to (-X2.13)
close
(-X2.11) to (-X2.12)
open
Circuit breaker
switched on
(-X2.11) to (-X2.13)
open
(-X2.11) to (-X2.12)
close