Original Operating Instructions
BATx0280-ES-1-400-1 (Outdoor)
Installation
O_BATx0280-ES-1-400-1_(Outdoor)_V1.3_GB
Page
29
of
69
3.5
Connections
DANGER!
Danger to life due to electric shock!
An incorrect selection and cable routing can cause damage to
property or serious injury or death to persons.
•
Wear suitable personal protective equipment for all work on the
product.
•
Selection and installation of electrical equipment, cables and
lines must comply to applicable local regulations and
standards.
•
Ensure that the diameter of the cables and lines matches the
diameters of the cable glands and connections.
•
Comply with the specified bend radii.
•
Offload the cables on both ends to relieve from pull and
pressure.
•
Route only one cable through each gland.
NOTICE
Damage of protection device!
All parameter changes to protection devices can cause damage.
•
Do not change the parameters of protection devices without
approval of the manufacturer.
•
Execute a trip test on the AC circuit breaker before
commissioning the product.
Cable requirements:
•
Compression cable lugs according to local regulations and standards.
•
Minimum degree of protection IP20
•
Cable entry grommets for AC connections and DC connections:
o
Minimum
: Ø 22 mm
o
Maximum
: Ø 36 mm
•
Parameters for cable sizing can be seen in Table 10.
Содержание BAT 0280-ES-1-400-1 Series
Страница 69: ......