Profibus DP – CBF-B1/CBFF-B1 Burner Control Box
vor00161
Device specific parameters must be considered during PROFIBUS-DP system configuration. In order to simplify this proc-
ess, CBF-B1/CBFF-B1 control boxes are supplied with a data file containing these parameters (GSD). The file format is
standardized and recognizable by other Profibus devices (masters/slaves). The bus interface will remain operable (online)
even if the CBF-/CBFF-B1 is turned off (stand-by mode) The setting of the Profibus addresses can be done by using the ad-
dress selector switches within the Profibus control box (Picture 2).
Picture 2 – Profibus address selectors:
Following tables showing data transmission between master and slave (CBF-B1/CBFF-B1).
Tab.2 : Output byte ( Master
→
CBF(F) :
Bit
Output byte AB0
0
Remote reset
1
Start (heat demand)
2
Cooling
3
Air purge
4
5
6
7
Tab.3: Input bytes (CBF(F)
→
Master ):
Bit
EB0
EB1
EB2
EB3
0
Operation burner
Manual mode
Status byte*
1
Fault burner
Cooling valve ON
2
Air valve ON
Safety interlock
3
Purge air ON
open
µA-flame signal
0...255,
255=25,5µA
4
Cooling ON
open
5
Flame mode ON (CBFF)
open
6
FLOX mode ON (CBFF)
open
7
Stand-by
open
*) see Tab.4
Configuration:
Address selector switches
10
1
10
0
+
( i.e. address 116 : B (11x 10
1
) + 6 (10
0
) = 110 + 6 = 116 )
Data Transmission (Bytes/Bits) from Master to CBF(F)-B1: