Parameter
Param.
Instance
Access
Description
Parameter Choices
Default
Setting
Default
Value
Data
Type
Configuration
configuration
1 bit per I/O point
0 = input
1 = output
BB#1
Watchdog
Action
13
Get/Set
Action taken on output
if no serial com with
Optomux
0x0000-0xFFFF
0x0000
0x0000
UINT
BB#1
Watchdog
Delay
14
Get/Set
Time until action is
taken on output if no
serial com with
Optomux in 10ms ticks
0-65535
in 10ms ticks
0 = Disabled
Disabled
0
USINT
BB#1 DN
Output Fault
Action
15
Get/Set
Output actions if no
DeviceNet
communications
0x0000-0xFFFF
1 bit per output:
0 = use fault value
1 = hold last state
Use Fault
Value
0x0000
UINT
BB#1 DN
Output Fault
Value
16
Get/Set
Output actions if no
DeviceNet
communications
0x0000-0xFFFF
1 bit per output:
0 = turn OFF
1 = turn ON
Turn OFF 0x0000
UINT
BB#1 DN
Output Idle
Action
17
Get/Set
Output actions when
DeviceNet in Idle
mode
0x0000-0xFFFF
1 bit per output:
0 = use Idle value
1 = hold last state
Use Idle
Value
0x0000
UINT
BB#1 DN
Output Idle
Value
18
Get/Set
Output actions when
DeviceNet in Idle
mode
0x0000-0xFFFF
1 bit per output:
0 = turn OFF
1 = turn ON
Turn OFF 0x0000
UINT
Note: Parameters 10 through 18 are repeated 9 more times for the other 9 brainboards that
can be on the JDO’s local network.
Example: Parameters 19,28,37,46,55,64,73,82,and 91 are the same as parameter 10 above.