SAFETY PRECAUTIONS  

INSTALLATION REGULATIONS

OIL FUMES OR LEAKS FROM THE APPLIANCE:

  

Extinguish any naked flames.

  

Open windows and doors.

  

Isolate the electrical supply.

  

Isolate the fuel supply to the boiler.

  

Rectify fault.

HEALTH & SAFETY:

The appliance contains no asbestos and no substances have been used in the construction

process that contravene the COSHH Regulations (Control of Substances Hazardous to Health

Regulations 1988). Where applicable, the CE mark indicates compliance with relative EU

Directives.

COMBUSTIBLE AND CORROSIVE MATERIALS:

Do not

store or use any combustible materials (paper, thinners, paints etc.) inside or within the

vicinity of the appliance.

The combustion air must be kept clear of chemically aggressive substances which can corrode

the appliance and invalidate any warranty.

FITTING & MODIFICATIONS:

Fitting the appliance and any controls to the appliance may only be carried out by a competent

engineer in accordance with these instructions and the relevant Installation Regulations.

Flue systems must not be modified in any way other than as described in the fitting instructions.

Any misuse or unauthorised modifications to the appliance, flue or associated components and

systems could invalidate the warranty. The manufacturer accepts no liability arising from any

such actions, excluding statutory rights.

SERVICING:

Advise the user to have the system regularly serviced by a competent, qualified engineer (such

as OFTEC registered personnel) using approved spares, to help maintain the economy, safety

and reliability of the appliance.

IMPORTANT:

This boiler must only be operated by a responsible adult who has been instructed in,
understands and is aware of the boiler’s operating conditions and effects. 

Failure to install appliances correctly could lead to
prosecution.

The appliance should be installed by a competent
person. The person installing the appliance should
be aware of the Health and Safety at Work Act and
take appropriate action to ensure that the
regulations are adhered to. In order to give
optimum efficiency and trouble free operation the
appliance must be commissioned by a qualified
OFTEC engineer.

The compliance with a British Standard does not,
in itself, confer immunity from legal obligations. In
particular the installation of this appliance must be
in accordance with the relevant requirements of the
following British Standards and regulations in
respect of the safe installation of equipment:
BS 5410: part 1: Code of practice for Oil Fired
Boilers.
BS 799: part 5: Specification for Oil Storage
Tanks.
BS 7593: Code of Practice for treatment of water
in domestic hot water central heating systems.
BS 5449: part 1: Specification for forced
circulation hot water central heating for domestic
premises.
BS 5955: part 8: Specification for the installation
of thermoplastic pipes and associated fittings for
use in domestic hot and cold water services and
heating systems.
BS 7291: Thermoplastic pipes and associated
fittings for hot and cold water for domestic
purposes and heating installations in buildings.
BS 7074: part 1: Application, selection and
installation of expansion vessels and ancillary
equipment for sealed water systems.
BS 7671:  IEE Wiring Regulations, current edition.
BS 1362: Specification for general purpose fuse
links for domestic and similar purposes.
The Building Regulations Part G, Part J and L1
England and Wales; Part F, Part G and Part J
Section III Scotland; Part L and Part F Northern
Ireland.
Local water company bye-laws.
The Control of Pollution (Oil) Regulations.
OFTEC Standards.
Where no specific instruction is given, reference
should be made to the relevant codes of practice.

Installations in Eire (Republic of Ireland)

The Installation must be performed by a 
competent and suitably trained person in 
accordance with the following Eire regulations.

Current Building Regulations -  
Republic of Ireland

ETCI rules for electrical installation

For further guidance see:

OFTEC Technical book three - 
Regional requirements: Republic of Ireland

8 716 106 256 C 03.10  30/3/10  14:24  Page 4

Содержание GREENSTAR UTILITY 18/25

Страница 1: ...ED CONDENSING BOILER CONVENTIONAL FLUE ROOM SEALED FLUE GREENSTAR UTILITY 18 25 FOR FULLY PUMPED OPEN VENT OR SEALED CENTRAL HEATING SYSTEMS AND DOMESTIC HOT WATER CYLINDERS UK THE APPLIANCE IS FOR US...

Страница 2: ...nd registered installers are able to certify that their work complies with building regulations Under the scheme OFTEC must be informed about every installation OFTEC will issue a building regulations...

Страница 3: ...6 CONVENTIONAL FLUE 17 ROOM SEALED FLUE OPTIONS 18 INSTALLATION UNPACKING THE BOILER 19 PIPEWORK POSITIONS FLUE OPENING 20 BOILER INSTALLATION 21 FLUE INSTALLATION 22 COMBUSTION CHAMBER 23 PIPEWORK CO...

Страница 4: ...ompetent person The person installing the appliance should be aware of the Health and Safety at Work Act and take appropriate action to ensure that the regulations are adhered to In order to give opti...

Страница 5: ...vent and sealed domestic central heating and mains fed hot water B Literature pack C Hardware pack including Condensate trap D Return pipe kit 855mm 600mm 370mm Check List Hardware Literature pack It...

Страница 6: ...Return mm Primary drain optional feed and expansion feed BSP Condensate polypropylene mm Electrical Electrical power supply voltage AC V Frequency Hz Max power consumption W Thermostats Boiler flow t...

Страница 7: ...8 REAR CABINET SUPPORT BRACKET 19 OIL ISOLATION VALVE 20 PRIMARY HEAT EXCHANGER 21 INTERNAL CONDENSATE TRAP 22 CONDENSATE OUTLET 23 BASE PLATE 24 COMBUSTION CHAMBER ACCESS DOOR 25 OVERHEAT RESET BUTTO...

Страница 8: ...SYSTEM Cleanse the system in accordance with BS 7593 Fill the system with cold mains water to the recommended pressure and check for leaks Open all drain cocks and drain the system Close drain cocks...

Страница 9: ...th at least a 3mm contact separation in both poles supplying the appliance Wiring between the appliance and the electrical supply must comply with IEE wiring regulations and any local regulations whic...

Страница 10: ...es Install a manual isolating valve B to the oil supply pipe H as close to the oil storage tank A as possible Fit an oil strainer and water separator C to the oil supply pipe near the oil storage tank...

Страница 11: ...s must be fitted with lockshield valves and left open All installations should have TRVs fitted to radiators within the sleeping accommodation An automatic bypass valve must be connected between the h...

Страница 12: ...AS approved Heating return Hose return Non return valve Non return valve Test cock Stop cock Water main supply Stop cock Temporary hose Heating return Auto air vent Non return valve Stop cock Make up...

Страница 13: ...of potentially harmful flue products escaping via the condensate route A Condensate from the boiler condensate trap supplied which has a 75mm minimum water seal B Sink C 21 5mm polypropylene condensa...

Страница 14: ...evel either direct to outside air or to a room Both vents must pass to the same room or be on the same wall to the outside air The minimum air vent free area is given in the table opposite a INSTALLAT...

Страница 15: ...be taken from a room or internal space containing a bath or shower and must not communicate with a protected area such as a hall stairway landing corridor lobby shaft etc Air vents must allow access...

Страница 16: ...d extending 300mm higher and wider than the tank is provided between the tank and the terminating position 4 Where a flue is terminated less than 600mm away from a projection above it and the projecti...

Страница 17: ...ust be sealed to prevent the leakage of condensate and combustion products Ensure that joints are made so that the condensate runs away and is not collected within the joint NOTE The flue can be incre...

Страница 18: ...e bend 45 E Vertical Terminal Kit incl 90 elbow Calculating the flue length Measure the total flue length required noting that the maximum straight flue length including the terminal is Horizontal 80...

Страница 19: ...ection cover from the boiler and place safely aside 3 Pull base of front panel E away from the boiler to disengage ball stud connectors Lift front panel E upwards off the top supporting ledge and stor...

Страница 20: ...y 52mm for every 1000mm of horizontal length that the flue opening is away from the boiler NOTE All horizontal flue sections must rise away from the boiler by 52mm per metre to ensure that condensate...

Страница 21: ...y away from the boiler 7 Release split pin to remove the flue thermostat M from the flue hood 8 Release split pins P Carefully remove the overheat thermostat phial Q automatic reset from the rear heat...

Страница 22: ...lbow Insert the flue elbow with its clamp loosely fitted then tighten the bracket screws N Clamp the elbow when adjusted to its required orientation If using an extension or horizontal terminal onto t...

Страница 23: ...ighten using the sequence shown in figure 3a until the chamber door is firmly secured do not over tighten the nuts 4 Unscrew screws E and remove flue manifold access cover F 5 Check that all the baffl...

Страница 24: ...ly pipe D along either side of the boiler as required and connect to the isolating valve E ensure the valve is closed NOTE Replace flexible hose at annual service to prevent possible oil leakage Conne...

Страница 25: ...a DANFOSS BFP 11 L3 Remove pump front cover A ensuring a suitable receptacle is used to catch any oil residue Remove changeover screw B Remove horseshoe washer C Refit changeover screw B Refit front...

Страница 26: ...split pin 4 Align burner combustion head N into boiler housing tube with gasket O correctly fitted Push firmly down to compress the gasket O Tighten burner retainers H sufficiently to ensure a good s...

Страница 27: ...te wires from cable end and strip to 6mm 230V connections 3 Connect SWITCHED LIVE wire Brown to terminal L Connect NEUTRAL wire Blue to terminal N Connect EARTH wire Green Yellow to the terminal Route...

Страница 28: ...INSTALLATION ELECTRICS 230V STANDARD WIRING DIAGRAM Key to components A EARTH STUD B HIGH LIMIT THERMOSTAT C BOILER MANUAL RESET OVERHEAT THERMOSTAT D FLUE MANUAL RESET OVERHEAT THERMOSTAT E TERMINAL...

Страница 29: ...e following Mains wiring 230V 50Hz Hot water tank thermostat Room thermostat System water valves Circulating pump External programmer E TERMINAL CONNECTOR BLOCK Remote 10 way junction box O requiremen...

Страница 30: ...y fitted and the connections are secure 4 Check the condensate pipework is correctly fitted and connected Check the condensate trap is filled with water IMPORTANT If the boiler is not to be commission...

Страница 31: ...Monitor the pressure gauge during venting and repressurise if required 3 Vent all radiators retighten when completed Check the system and correct any leaks Bleed air from at least one of the secondary...

Страница 32: ...ct a spare flexible oil hose I to discharge into container H Open the isolating valve turn on the power to the boiler and set the programmer to ON Prime the de aerator until there is a steady flow of...

Страница 33: ...button E to initiate another start sequence Repeat procedure until a flame is established 3 Start and run for 3 minutes then switch off Check for after spurting from the nozzle indicated by oil satura...

Страница 34: ...ly and balance the system to the temperature difference required for the heating flow and return according to the heating load 2 Set the room thermostat to minimum The burner and circulating pump shou...

Страница 35: ...conditions to the heating system in accordance with the manufacturers instructions The inhibitor or combined inhibitor anti freeze must not cause damage to the materials within the boiler mild steel s...

Страница 36: ...the Guarantee Registration Card Combustion Record at the rear of this manual and CD11 or an equivalent commissioning form Set up the controls and show the user how to operate all the controls shown in...

Страница 37: ...em and note any faults which may need to be corrected during the service Switch off and electrically isolate the boiler 4 Depress locking ears and unplug burner lead F from control box G 5 RS flue onl...

Страница 38: ...oil atomising nozzle E DO NOT dismantle the nozzle and DO NOT clean the nozzle tip Check the electrodes F and reset if necessary as shown opposite Refit the combustion head Check that the nozzle E lie...

Страница 39: ...solvent free grease Refit the trap making sure that the locking tabs are locked in place Pour 500ml of water into drain E to refill the condensate trap Clean the secondary heat exchanger baffles D if...

Страница 40: ...p edge of panel E onto the top supporting ledge D on the boiler Locate the ball stud connections K at the base of the front panel E and push towards the boiler to secure Align top front panel H and pu...

Страница 41: ...rt Number 8 716 107 621 0 11 Auto reset High Limit thermostat Part Number 8 716 107 623 0 12 Manual reset High Limit thermostat Part Number 8 716 107 625 0 13 Manual reset flue thermostat Part Number...

Страница 42: ...8 0 11 Flexible oil hose kit Part Number 8 716 115 312 0 12 Burner O ring gasket Part Number 8 716 140 902 0 13 Boiler control thermostat Part Number 8 716 107 621 0 14 Auto reset High Limit thermosta...

Страница 43: ...e settings incorrect Set up as in installation instructions Faulty ignition transformer Replace Open circuit ignition Check and replace electrodes or high tension leads if necessary Faulty control box...

Страница 44: ...g incorrect Correct burner rating Boiler thermostat differential incorrect Replace boiler thermostat External controls not operating correctly Check and correct external controls OIL SMELLS Blocked fl...

Страница 45: ...ition GREEN RED Under voltage or over voltage RED ORANGE lock out for no flame during safety time RED Lock out for false flame signal RED Flashing Lock out for burner control error Lock out for maximu...

Страница 46: ...or reposition terminal If BF Remove burner snorkel tube retest Lights OK FAULT FINDING LOGIC FOR RIELLO CONTROL BOXES All resistance measurements are actual measured values and some variation is to b...

Страница 47: ...Yes Yes Yes No Yes Yes Yes Yes No No No Yes Yes Yes Yes No No No No No Yes Yes Yes Yes Yes No No No No Yes Yes Yes Yes Replace lead No FAULT FINDING LOGIC FOR SATRONIC CONTROL BOX Note This chart ass...

Страница 48: ...YES NO WHAT TYPE OF SCALE REDUCER HAS BEEN FITTED FOR THE DOMESTIC HOT WATER MODE MEASURE RECORD WATER FLOW RATE lts min CONFIRM THE FOLLOWING THE HEATING AND HOT WATER SYSTEM COMPLIES WITH CURRENT BU...

Страница 49: ...PRESSURE psi CO2 NOZZLECHANGED YES NO F G T C FLUEPRESSURE COMMENTS SIGNATURE SERVICE 6 DATE ENGINEERNAME COMPANYNAME TELNo OFTECREGNo PUMPPRESSURE psi CO2 NOZZLECHANGED YES NO F G T C FLUEPRESSURE CO...

Страница 50: ...NOTES NOTES NOTES INSTALLATION SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR DANESMOOR UTILITY 18 25 8 716 106 256C 03 2010 50 8 716 106 256 C 03 10 30 3 10 14 24 Page 50...

Страница 51: ...NOTES NOTES INSTALLATION SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR DANESMOOR UTILITY 18 25 8 716 106 256C 03 2010 51 NOTES 8 716 106 256 C 03 10 30 3 10 14 24 Page 51...

Страница 52: ...valve if fitted should be removed from the oil dip pipe Boiler locks out at the start of a demand Heating off overnight for example 1 If an air eliminator is being used check that there are no leaks...

Отзывы: