Pre-Installation

 

Greenstar Oilfit Flexi CF Flue – 6720807911 2019/05

8

3

Pre-Installation

3.1

Typical installations

WARNING: 

Open flue

▶ Open (conventional) flued appliances must not be installed in 

bedrooms, bathrooms or bedsitting rooms

▶ Inspection points must be provided for access to check the flue 

system joints.

Before starting installation, check that:

• the chimney is structurally sound and free from obstructions
• the chimney has been swept to remove deposits since the last use

This flexible flue pipe is only suitable for lining chimneys that conform to 
the Building Regulations and it should not be used as a chimney on its 
own or outside a masonry or flue block chimney.

All the flexible liner and adaptors must be within the chimney, with rigid 
stainless steel flue pipe connecting to the boiler.

The first 600mm of the stainless steel flue pipe from the boiler must be 
vertical with no bends or restrictions.

There must be a least a 25mm clearance between the S/S flue pipe and 
any combustible material.

The data label must be secured onto the chimney or chimney hearth 
using the plate provided.

If it is not possible to attach the plate to the chimney, the plate can be 
attached, in a visible position, next to the electricity consumer unit.

Do not attach the data plate or label to the flue system.

The terminal should not be modified and an extra cowl or cover must not 
be fitted, the boiler is designed so that any rain that enters the flue will 
be directed down to the condensate drain.

Calculating the flue length

Refer to figure 8 and table 2

L max = boiler max minus 1 metre*.

(Each 45° bend has a 0.5 metre equivalent flue length).

* If the chimney has an additional offset, then L will be reduced by an 
extra metre.

** The top 45° bend may not be required if there is sufficient room in the 
chimney to turn the flexible liner through 45° within the chimney. The 
stainless steel section must be adequately supported.

# Maximum flue length without damper is 6 metres

Table 2   Max flue lengths

Fig. 8  

Typical installation - offset flue

[1]

Chimney cowl

[2]

Flexible liner

[3]

Centralising spacer

[4]

Fire stop/Inspection plate

[5]

Maximum two bends at 135°

[6]

Stainless steel vertical section (minimum 600mm)

[7]

Boiler

Greenstar boiler 
models

Model FlueØ  

mm

Max flue 

length (m)

Damper 

required >6m

Camray kitchen

12/18

100

15

N

18/25

100

15#

Y

25/32

100

15#

Y

Camray Utility & Utility 
System

12/18

100

15

N

18/25

100

15#

Y

25/32

100

15#

Y

Danesmoor (pre 2011) 18/25

100

15

N

Heatslave

12/18

100

15

N

18/25

100

15

N

25/32

100

15

N

Utility

18/25

100

15

N

32/50

100

15

N

50/70

100

15

N

Heatslave II

12/18

100

12

N

18/25

100

12

N

25/32

100

12

N

Danesmoor 
(cross firing post 2013)

12/18

100

12

N

18/25

100

12

N

25/32

100

12

N

Greenstar boiler 
models

Model FlueØ  

mm

Max flue 

length (m)

Damper 

required >6m

**

MAX

L

0010028942-001

MIN

600mm

1

2

4

7

6

5

3

Содержание Greenstar Oilfit Flexi CF Flue

Страница 1: ...6720807911 2019 05 UK IE Flue kit installation instructions Floor standing oil condensing appliance flue Greenstar Oilfit Flexi CF Flue 0010028877 001 Conventional Flexible Flue Liner...

Страница 2: ...ns in conjunction with the appliance Installation and maintenance instructions manual carefully before starting installation Observe all the safety precautions described in the Installation and mainte...

Страница 3: ...Carefully unpack the unit Ensure that all packaging material is removed and that the unit is free from all materials that may prevent the unit from operating correctly 1 3 Requirements Installation Th...

Страница 4: ...components 100mm Chimney gasket The self adhesive chimney gasket does not have to be used but may be required if there are large irregularities on the chimney top face Fig 3 CF Flexible flue liner co...

Страница 5: ...nsion kit Part number 7 716 190 067 2 1000mm x 100mm Stainless steel extension kit Part number 7 716 190 066 3 500mm 1000mm x 100mm Stainless telescopic steel extension kit Part number 7 716 190 068 4...

Страница 6: ...sket does not have to be used but may be required if there are large irregularities on the chimney top face Fig 6 CF Flexible flue liner components 130mm 1 Chimney cowl 2 Chimney gasket 3 Terminal 4 S...

Страница 7: ...xtension kit Part number 7 716 190 071 2 1000mm x 130mm Stainless steel extension kit Part number 7 716 190 070 3 500mm 1000mm x 130mm Stainless telescopic steel extension kit Part number 7 716 190 07...

Страница 8: ...The terminal should not be modified and an extra cowl or cover must not be fitted the boiler is designed so that any rain that enters the flue will be directed down to the condensate drain Calculatin...

Страница 9: ...p Inspection plate 5 Fire stop plate 6 Stainless steel vertical section minimum 600mm 7 Boiler NOTICE Fire stop plates Depending upon the opening situation a fire stop plate as shown can be used Fig 1...

Страница 10: ...nofthesupportbrackets 3 forthefirstfluesection 2 on the chimney wall Drill the chimney wall and fit the support bracket 3 using the wall plug and screw provided On some installations it will be necess...

Страница 11: ...ottom of the liner should be cut off tidily at the start of a corrugated section shown in the figure below 3 Where the bend in the chimney is 500mm or less follow the advice in figure 14 or if the ben...

Страница 12: ...r until the adaptor bottoms out Ensure that the flexible flue is pushed fully down is square with the adaptor 3 Push the locking tabs in the direction of the arrow until they click and lock in place 4...

Страница 13: ...2 Chimney support bracket 3 Silicon grease 4 Seal 5 Adaptor assembly 4 5 Fitting the chimney cowl The terminal flue end must be at least 350mm long Ensure that the chimney bracket is larger than the c...

Страница 14: ...the chimney plate either next to the boiler chimney or next to the electricity consumer unit The plate can either be stuck to a flat sound surface or fitted to the mounting plate and screwed in place...

Страница 15: ...Installation 15 Greenstar Oilfit Flexi CF Flue 6720807911 2019 05...

Страница 16: ...Kingdom Tel 0330 123 9559 worcester bosch co uk TECHNICAL SUPPORT 0330 123 3366 RENEWABLE SUPPORT 0330 123 9229 CONTROLS AND CONNECTIVITY TEAM 0330 123 3641 APPOINTMENTS 0330 123 9339 SPARES 0330 123...

Отзывы: