Plume management system
11
Greenstar Condensfit II – 6 721 819 755 (2019/12)
5
Plume management system
5.1
Plume management product information
Plume management kit - 7 716 191 086
Fig. 24 60mm plume management kit components
[1]
Terminal elbow
[2]
Extension 500mm
[3]
Outlet assembly
[4]
Support bracket
60mm plume management accessories
Table 4
Fig. 25 Plume management accessories
5.2
Plume management options and measurements
WARNING:
Minimum plume management length:
A minimum measured distance of 500mm must be maintained between
air inlet and exhaust.
▶ Do not terminate the plume management inside the terminal
exclusion zone (shaded area) shown in figure 26.
NOTICE:
Plume management length:
▶ The plume management length must be a minimum of 500mm. The
plume management length must not exceed the maximum straight
length for a horizontal Ø 60/ 100mm flue with a 60mm plume
management system. The maximum Ø 60/ 100mm flue lengths are
stated in the relevant appliance Installation and maintenance
instructions.
Horizontal plume management runs:
▶ The initial run from the terminal elbow must have a minimum of a 10°
fall back, to the appliance for proper disposal of condensate (stop
tabs in the elbow ensure that fall back is not less than 10°).
▶ Any further runs after an elbow must be at least 3° fall back to the
appliance.
Effective plume management length:
▶ Because of the longer terminal end, two 45° bends must be employed
to bring the plume management close enough to the wall for a
support clamp to be fitted.
▶ The 45° bends can found in the 60mm plume management accessory
kit.
▶ The effective length of the minimum measured 500mm will be two
45° bends at 1,500mm effective length plus a straight piece of plume
extension, at approximately 300mm.
This will achieve a measured 500mm from the flue inlet, but an
effective length of 1,800mm. This must be taken into account when
calculating the effective total length of the plume management.
Fig. 26 Terminal exclusion zone
5.2.1
Example plume management installation options
1
1000mm extension with support clamp 7 716 191 087
2
90° elbow
7 716 191 088
3
45° elbow (set of 2)
7 716 191 089
4
Support bracket
8 716 111 275 0
1
2
3
4
0010013546-001
4
3
2
1
0010032817-001
M Plume management effective length
X
Terminal exclusion zone
1
Terminal elbow
2
Extension 500mm
3
Outlet assembly/90° elbow
0010031819-001
±80°
500
mm
500m
m
500m
m