Inspection and maintenance
Greenstar 8000 Life – 6720883865 (2019/02)
50
Fig. 70 Removing bottom panel
Removing front cover
1. Remove screw from bottom of front panel
2. Push in the green clips securing both sides the outer case.
3. Pull bottom of front cover forwards and upwards to release the clip on
top of the boiler and remove outer case.
Fig. 71 Removing outer case
8.5
Fan pressure test
NOTICE:
Fan pressure test
▶ The appliance must be running at maximum output in chimney sweep
mode for the fan pressure test, (
chapter 6.4).
Fig. 72 Fan pressure test point
This test is to determine if the heat exchanger requires cleaning or
additional actions.
Fan pressure test reading.
▶ The pressure reading will be in negative values.