Does the fan run
before the fault
occurs?
Turn off boiler. Is there
continuity across the
C
and
NO
terminals of
the air pressure switch
(where green wires are
fitted)?
Remove the fan
connector from board
position
ST1
and
restart the boiler. Is
there mains 230V
across the centre (
L
)
and left (
N
) tracks at
ST1
? Note: Take care
not to short
L
to
N
.
Repair or replace fan
(Section 14.3.3) or
cable.
Air pressure switch
is shorting.
Replace switch.
Section 14.3.2)
Replace control board.
(Section 14.3.23).
FAIL POINT J “Air Pr
essur
e F
ault”
No
No
No
Yes
Yes
Yes
Remove electrical
connectors from
pressure switch and
restart boiler. Is there
continuity between
C
and
NO
terminal
(where green wires
were fitted) when the
fan runs?
Pressure switch has
not closed. Are the
silicon tubes in good
condition and free of
condensation.
Replace air pressure
switch (Section
14.3.2). Note: In the
unlikely event of this
not solving the
problem inspect the
pressure pick-up
(Venturi) in the fan.
Inspect condensate
drain. Is it free from
any restrictions?
Inspect the flue. Is it
free of any
restrictions?
Rectify flue problem.
Clean condensate drain
Remove multiway
connector from board
position
ST16
. Is there
continuity of the
green wires?
Replace control board.
(Section (14.3.23).
Repair wires or replace
harness.
Replace tubes. If
condensation has
occurred, also replace
pressure switch and
check condition of
Venturi in the fan.