Does this fault occur in
only one of the operating
modes? CH or DHW
Replace control board
(Section 16.4.23).
Replace control board
(Section 16.4.23).
Replace control board
(Section 16.4.23).
Replace air pressure
switch (Section 16.4.2).
Note: In the unlikely
event of this not solving
the problem inspect the
pressure pick-up (Venturi)
in the fan.
Repair or replace fan
(Section 16.4.3) or
cable.
Repair or replace fan
(Section 16.4.3) or
cable.
Air pressure switch
is shorting
Replace switch
(Section 16.4.2).
28CDi and 35CDi
II
24CDi,28CDi and 35CDi
II
Remove fan connector
from board position ST1
and restart boiler in the
fault mode.
After 5 seconds is there
mains 230V from the left
(N) track at ST1 and right
(L) track if DHW mode?
Centre (L) track if CH
mode?