Worcester 14/19CBi Скачать руководство пользователя страница 20

11.2.6                Telescopic Horizontal Flue Kit up to

750mm in Length

(i)

The standard flue can be telescopically adjusted to any 
length between 425mm and 725mm.
It will only be necessary to cut the standard assembly if 
L<425mm. Cut the flue turret assembly and the terminal 
assembly by the same amount i.e L=350 - remove 75mm 
from each assembly.
The minimum length L is 250mm with cutting.

General:

Cut the ducts as necessary, ensuring that the ducts are

square and free from burrs. Always check the dimensions before
cutting.

(i)

Fix the flue assembly together using the self-tapping 
screws provided. Refer to Fig. 21, 22.

(ii)

Apply the plastic tape onto the duct in contact with the 
wall (see Fig. 21, 22).

If an internal fitting kit is to be used refer now to Section 11.2.10
otherwise refer to Section 11.2.11. 

11.2.7                  Telescopic Horizontal flue Kit 

Greater Than 750mm in Length

If bends are to be used refer also to Section 11.2.8.

(i)

By adding extension duct kits to the standard flue kit it is 
not necessary to cut the extension ducts if

L is between 
1175 - 1475mm

(1 extension)

1925 - 2225mm

(2 extension)

(ii)

However extension ducts need to be cut if

L is between

725 -    1175mm

(1 extension)

1475 -  1925mm (2 extension)
2225 -  2500mm (3 extension) 19/24 CBi

2225 - 2975mm

(3 extension) 14/19 and 19/24CBi

(iii)

To shorten the duct the first extension only should be cut. 
To work out the length to be cut off:
(No. of extensions x 750) + 425 — L = length to be cut.

NOTE:

Extension duct measurements do not include the 

socketed end. Unless specifically instructed the socketed 
end must not be removed.

(iv)

Fix the flue assembly together using the self tapping 
screws provided (see Fig. 20).

(v)

Apply the plastic tape onto the duct in contact with the 
wall (see Fig. 20).

If an internal fitting kit is to be used refer now to Section 11.2.10
otherwise refer to Section 11.2.11.

11.2.8  Flue Bends

90° and 45° directional bends are available. A maximum of two
45° or 90° bends may be used in addition to the first bend on
the flue turret.
A  90° bend is equivalent to 750mm of straight duct.
A 45° bend is equivalent to 0.375m of straight duct. 

Measure the lengths X and Y. Refer to Fig.23.
The  maximum  value  of  X  using  the  turret  assembly  only  is
506mm.  Reduce  the  ducts  to  the  appropriate  length  e.g.  X  =
406mm, cut 100mm from the air duct and 120mm (to cover the
entry  into  the  45°  or  90°  elbow)  from  the  flue  duct.  Refer  to
Fig.24.

The final section, dimension Y, of the flue system must include a
section of plain duct assembly i.e . an extension  assembly with
the  sockets  removed.  Reduce  the  final  section,  including  the
terminal  assembly,  by  the  appropriate  amount  i.e.  Air  duct  Y  -
81mm and the flue duct Y - 51mm. Refer to Fig.23.

If Y is smaller than425mm it will be necessary to cut the air and
flue  ducts  of  the  extension  to  a  plain  length  of  100mm  and
reduce  the  length  of  the  terminal  assembly  e.g.  Y=350mm  -
remove 75mm from the terminal assembly.

If  Y  is  between  425  and  725mm  it  is  not  necessary  to  cut  the
terminal assembly or use a second extension duct as the length
can be set telescopically.

If Y is greater than 725mm then two extension duct assemblies
will  be  required,  the  first  assembly  being  cut  to  length  as  plain
tubes.

If  more  than  two  extension  ducts  are  needed  in  any  section  to
achieve  the  required  length  then  the  final  section  of  the
assembly  must  not  be  less  than  325mm  without  cutting  the
terminal assembly.
NOTE: The flue duct of the final extension must be 30mm longer
than the air duct.

Each  section  must  be  connected  to  the  previous  section  of  the
flue  bend  by  fixing  the  flue  ducts  together  and  then  similarly
fixing the air ducts which engage the elbows.

Fix  the  flue  assembly  together  using  the  self  tapping  screws
provided.

Apply the plastic tape onto the duct in contact with the wall (see
Fig. 23).

If an internal fitting kit is to be used refer now to Section 11.2.10
otherwise refer to Section 11.2.11.

20

Fig. 23. Flue bends.

Air  Y

– 8

1mm

Flue  Y

– 5

1mm

Y

X

Tape 

Swaged ends 

Plain ends 

Note:

Connections to and from

bend should be plain ended and
the same length.  

Содержание 14/19CBi

Страница 1: ...PPLY OF DOMESTIC HOT WATER INSTALLATION AND SERVICING INSTRUCTIONS This appliance is for use with Natural Gas or LPG Cat II 2H3P 9 14CBi GC NUMBER 41 311 50 N G 9 14CBi GC NUMBER 41 311 51 LPG 14 19CBi GC NUMBER 41 311 52 N G 14 19CBi GC NUMBER 41 311 53 LPG 19 24CBi GC NUMBER 41 311 54 N G 19 24CBi GC NUMBER 41 311 55 LPG APPLIANCE OUTPUTS IMPORTANT THESE INSTRUCTIONS APPLY IN THE UK ONLY AND MUS...

Страница 2: ...he or she must call back the installer who has not fulfilled his obligations to record the information required by the initiative 2 1 General Information The Worcester boilers provide a heat output of between 9 14kW 9 14CBi 14 19kW 14 19CBi 19 24kW 19 24 CBi factory set at mid range and contain a temperature control and all the appropriate safety controls They are suitable for fully pumped open ve...

Страница 3: ...nue to run for up to 4 minutes and the fan for 1 minute to dissipate the residual heat Domestic Hot Water The supply of domestic hot water depends upon the type of hot water equipment installed and the control system The use of unvented cylinders must be in accordance with the manufacturers instructions and relevant to British Standards The boiler is despatched from the factory with the flow and r...

Страница 4: ...5 2 18 16 52 17 96 8 5 1 90 14 00 15 38 6 0 1 63 23 45 25 74 12 0 2 72 21 25 23 35 9 8 2 47 19 05 21 16 7 8 2 24 14 00 15 28 27 2 0 63 12 00 13 18 20 4 0 54 10 00 11 17 15 4 0 45 19 05 20 57 25 4 0 84 16 52 17 96 19 0 0 73 14 00 15 38 13 9 0 63 23 45 25 74 29 9 1 05 21 25 23 35 24 6 0 96 19 05 21 16 20 2 0 87 Table 1 Factory set at maximum input BURNER PRESSURE Natural Gas Net Input Gross Input x ...

Страница 5: ...RE Sealed System 2 5 bar MINIMUM CENTRAL HEATING SYSTEM SET PRESSURE Sealed System 0 12 bar OUTPUT TO CENTRAL HEATING 9 14CBi 9 0 14 0kw 14 19CBi 14 0 19 05kw 19 24CBi 19 05 23 45kw NOx CLASSIFICATION FOR CBi APPLIANCES Class 1 SEDBUK NUMBER AND BAND 9 14CBi NG 78 5 D 14 19CBi NG 79 4 D 19 24CBi NG 78 4 D 9 14CBi LPG 81 0 D 14 19CBi LPG 81 7 D 19 24CBi LPG 80 8 D Table 5 Improved access 50mm is re...

Страница 6: ...und on the opposite side The appliance is NOT suitable for external installation The wall must be able to support the weight of the appliance Refer to Table 4 The specified clearances must be available for installation and servicing Refer to Table 7 and Fig 2 The appliance can be installed in a cupboard compartment to be used for airing clothes providing that the requirements of BS6798 and BS5440 ...

Страница 7: ... stated in the table above minimum clearances are given in Section 4 Siting the Appliance then permanent air vents for cooling are required one at high level and one at low level Both high and low level vents must communicate with the same room or must be on the same wall to outside air The minimum requirements are 6 Air Supply 5 Flue terminal positions 7 L L K K F F G A M E J F HI D G A B C Fig 4...

Страница 8: ...d filling kit Refer to Fig 8 The appliance must not be operated without the system being full of water and correctly pressurised All connections in the system must withstand a pressure of up to 3 bar The system and the appliance must be properly vented Repeated venting loses water from the system and usually indicates that there is a leak It is NOT suitable for direct water supply Do not connect t...

Страница 9: ...ion Vessel For system wiring please refer to Fig 10 and the controls manufacturers details Bypass balancing valve or bathroom radiatior with two lockshield valves Pressure Gauge Relief Valve Fig 8 Sealed system filling and make up Primary cold feed 15mm min Heating vent 22mm min Feed and Vent Cistern Diverting valves Boiler Pump Radiator S H Minimum static head 1 2m measured from the highest point...

Страница 10: ...entre must be through a common fused double pole isolator situated adjacent to the appliance The isolator must have a contact separation of 3mm minimum in all poles A single switched live cable should be wired into the boiler from the system wiring centre The mains and pump cables must be fed through the mains lead bracket secured through the cable clamp and connected to the connector plug Refer t...

Страница 11: ...3 X4 X5 X6 1 orange 1 1 X7 User control potentiometer switch black white brown grey violet red violet red black orange brown grey white NC NO COM Temperature sensor Pump Live Pump Neutral Permanent Neutral Permanent Live Switched Live Boiler Demand earth Installer Connections blue brown Polarity of these connections is not important 3 pin header ...

Страница 12: ... wiring centre L switched Pump not to be connected to system wiring centre Pump supplied from boiler only L N E Timer Room thermostat Tank thermostat System water valves 230V 50Hz 5A Fuse System components wired into terminal strip in accordance with component manufacturers instructions Frost stat Common isolator for wiring centre and boiler Should be located adjacent to the boiler MainsEarth TOPC...

Страница 13: ...screw 9 Cabinet fixing screw 10 Gas valve 11 Spark electrode 12 Burner injector 13 Temperature sensor 14 Overheat thermostat 15 Air pressure switch 16 Flow pipe 17 Return pipe 18 Combustion test point 19 Sensing tubes 20 Fan 21 Flue hood 22 Inner case cover fixing points 4 23 Outer case earth tag 24 Side cover plate 25 Wire clip 26 Pressure tube junction 1 2 22 3 4 5 6 7 8 9 10 11 12 13 14 15 16 1...

Страница 14: ...ture sensor 14 Overheat thermostat 15 Air pressure switch 16 Flow pipe 17 Return pipe 18 Combustion test point 19 Sensing tubes 20 Fan 21 Fan clamp 2 screws 22 Inner case cover fixing points 4 23 Flue hood 24 Outer case earth tag 25 Side cover plate 26 Wire clip 27 Front baffle Fig 12b Boiler Assembly 14 19 and 19 24CBi Shown set for external flue turret kit or vertical flue 1 2 23 22 3 4 5 6 7 8 ...

Страница 15: ...e at 110mm diameter ii Fix the wall mounting plate do not fully tighten the screws iii Measure the wall thickness L Min 220mm Max 375mm If L is less than 220mm thick then it is necessary to cut the flue To do this subtract L from 220 and cut all flue parts by this amount Ensure that the ducts are square and free from burrs Always check dimensions before cutting The minimum length L is 100mm with c...

Страница 16: ...to position so that the holes in the flange line up with those in the case NOTE The correct rectangular flue restrictor must now be fitted when the boiler is on the wall 9 14CBi and 14 19CBi 19 24CBi 66 X 62 Rectangular 77 X 62 Rectangular ii From the inside place the correct restrictor in position over the flue opening and using the screws provided fix through the inner casing into the flue syste...

Страница 17: ...essure tube extension 2 3 red tube 4 clear tube 5 7 Fig 16 Fan Flue hood Assembly with Rear Only Flue Kit 6 NOTE The polarity of wires is not important 9 10 8 ve ve 11 12 Fig 15 Fixing the appliance to the wall mounting plate 1 2 6 3 4 5 7 8 1 Telescopic flue assembly 2 Wall mounting plate 3 Fixing or security screw 4 Leveling feet 2 5 Restrictor plate with rectangular hole 6 Gasket 7 Flue fixing ...

Страница 18: ...ecurity bolt Drill the 5 fixing holes 60mm deep for the No 12 size plugs 11 2 4 Boiler Preparation i Remove the appliance casing by releasing the screw at the centre base Disconnect the earth connection at the base and lift off ii Release the four screws and remove the inner casing cover iii Release the two wing nuts and remove the combustion chamber front panel The cover is located into notches a...

Страница 19: ...5 2 2225 3 2500 19 24CBi 3 2975 9 14 and 14 19CBi iv Measure length L Refer to Fig 20 21 22 v For installation of standard flue up to 750mm refer to Section 11 2 6 For installation of flue greater than 750mm refer to Section 11 2 7 For installation of bend kits refer to Sections above and Section 11 2 8 For installation of vertical adaptor refer to Section 11 2 9 For installation of internal fitti...

Страница 20: ...bends may be used in addition to the first bend on the flue turret A 90 bend is equivalent to 750mm of straight duct A 45 bend is equivalent to 0 375m of straight duct Measure the lengths X and Y Refer to Fig 23 The maximum value of X using the turret assembly only is 506mm Reduce the ducts to the appropriate length e g X 406mm cut 100mm from the air duct and 120mm to cover the entry into the 45 o...

Страница 21: ...he flue centring ring 11 2 11 Install the Boiler IMPORTANT Thoroughly flush the system before connecting the boiler Any system cleanser must be fully flushed from the system i Lift the boiler onto the wall mounting plate See Fig 27 ii Level the boiler using the two levelling feet at the base of the back panel iii Fit the bottom fixing screw or optional security screw iv Connect the gas supply usin...

Страница 22: ... door 11 2 13 Completion of the Installation Check that all the gas and water connections have been tightened Lower the base plate control panel Refer to Fig 30 The permanent mains and switched live supply to the boiler must come from the system junction box Refer to Fig 11 A 4 core cable is recommended Feed the 4 core cable and the pump cables through the bracket and secure in the cable clamp Ref...

Страница 23: ...mes before going to lockout To reset the product turn the control knob fully anti clockwise and back NOTE The burner pressure is factory set and may be reset to match the system requirements If after checking that the supply pressure is sufficient i e 19 mbar approx NG or 36 mbar approx PROPANE at the gas valve inlet pressure test point the required pressure cannot be obtained then contact Worcest...

Страница 24: ...plies are isolated before accessing the following parts Remove some or all of the following parts to gain access to the components Outer Case Loosen the screw and clip at the base disconnect the earth tag lift the case up and pull forwards Base Control Assembly Remove the single screw and lower Refer to Fig 33a b Inner Case Door Remove the two top corner screws Loosen the two bottom corner screws ...

Страница 25: ...tter access The front and rear flueways can be cleaned with a brush being careful to protect the rear combution chamber insulation The inner flueway can be cleaned with a scraper Check the combustion chamber insulation and replace if there is any sign of damage or deterioration Refer to Section 15 4 11 Carefully refit any components removed and check that all screws are tight and the connections p...

Страница 26: ...might retain water 15 4 Component Replacement Replace any components removed from the appliance in the reverse order using new gaskets O rings sealant heat transfer paste where necessary Always check that any electrical connections are correctly made and that all screws are tight 15 Replacement Of Parts 26 1 Inner case 8 Base controls fixing screw 2 J bolts and wing nuts 2 9 Cabinet fixing screw 3...

Страница 27: ...tat 15 Casing support 16 Return pipe 17 Flow pipe 18 Air pressure switch 19 Combustion test point 20 Air pressure switch fixing clip 4 21 Flue hood 22 Fan 23 Sensing tubes 24 Outer case earth tag 25 Side cover plate 4 5 6 7 8 7 9 8 10 14 15 11 12 14 11 16 17 18 19 20 21 22 23 Fig 35 Base Control Board Assembly 1 2 3 4 5 6 7 8 1 Base control assembly 2 Base control assembly fixing point 3 Gas valve...

Страница 28: ...ata plate on the cabinet where required pressure will be indicated Alter the red arrow if a new setting is made The adjustment screw must be sealed by a dab of paint to stop unauthorized adjustment Switch off the appliance disconnect the pressure gauge and tighten the test point screw Refer to Fig 31 Check for gas soundness 15 4 2 Spark Electrode Remove the inner casing cover and the combustion ch...

Страница 29: ...ections are correctly made to the new fan Refer to Fig 37 and 37a Do not use any sealant on the fan flue duct connection The polarity of wires onto the fan is not important 29 1 1 Flue hood 2 Fan 3 Sensing connection 4 Sensing connection 5 Flue turret 6 Fan clamp 7 Fan clamp fixing screw 2 3 red tube 4 clear tube 5 6 7 Fig 37 Fan Flue hood Assembly with External Flue 1 1 Flue hood 2 Fan 3 Sensing ...

Страница 30: ...he position of each pressure tube carefully disconnect the tubes and electrical connections from the switch Unclip and remove the switch if there is more than 50mm clearance Refer to Fig 40 If there is minimum clearance then remove the inner casing cover and release the two screws Remove the air pressure switch and mounting bracket complete Ensure that the connections are correctly made on the rep...

Страница 31: ...ly burner blade assembly and the access plate at the left hand side of the inner casing Pull off the leads from the sensor and overheat thermostats Pull off the clip to remove the sensor unscrew the overheat thermostat Pull out the clips securing the flow and return pipes and remove them from the manifolds It will be necessary to disconnect the pipes from the system adjacent to the boiler Unscrew ...

Страница 32: ... cover IX Switch on the gas supply and open the gas cock at the appliance Check for leaks at the gas valve inlet X Refit the base control assembly XI Recommission the appliance Refer to Section 12 Commissioning for details Adjust the burner setting pressure as required Refer to Table 1 and Fig 31 XII Fix the Red Arrow on the data plate to show the boiler setting If the setting has been altered the...

Страница 33: ...ctrode Assembly 1 87161421400 9 E60 481 Sensor Electrode Assembly 1 87161421390 10 E60 482 Spark Electrode Lead 1 87161218050 11 E60 483 Sensor Electrode Lead 1 87161421370 12 E60 484 Heat Exchanger Assembly 9 14CBi 1 87161216990 13 E60 485 Heat Exchanger Assembly 14 19 19 24CBi 1 87161217000 14 E60 486 Insulation Kit 9 14CBi 1 77161018540 15 E60 487 Insulation Kit 14 19 19 24CBi 1 77161017960 16 ...

Страница 34: ...run Boiler demand light on Pump supply on Ignition sequence Boiler cycles to satisfy temperature set by facia control knob Temperature Sensor disconnected Ignition sequence inhibited fan and pump may run for short period Boiler overheat Overheat thermostat trip Lockout light constant Protection Systems re attempt ignition MAX 4 times lockout light flashing Fan continues for 1 minute FAIL PASS PASS...

Страница 35: ...ystem checks are the first electrical checks to be carried out during a fault finding procedure On completion of the Service Fault finding task which has required the breaking and remaking of electrical connections check a EARTH CONTINUITY b SHORT CIRCUIT CHECK c POLARITY and d RESISTANCE TO EARTH WARNING In addition to the controls the overheat thermostat and fan are connected directly to the per...

Страница 36: ...ate electrical supply from external system No Create a new demand Does the fan run Yes No Is there 230V across the fan terminals WARNING if NO both fan terminals will be LIVE Does the pump run Check fuse F1 on the control board Has it blown No No No Replace fan Yes Air pressure switch is stuck on Replace air pressure switch Yes Replace fuse and investigate cause Suggestions connections to or fault...

Страница 37: ...oiler demand With the boiler cool does the pump run Yes Switch off mains supply Remove boiler cover and inspect the temperature sensor Is it correctly fitted to the manifold with heat conductive paste on its surface Yes Gain access to control board and inspect the slide switch at the front of the board In normal domestic installation this switch should be in the left normal position Yes Yes Yes Re...

Страница 38: ... leads Yes Replace control board Yes During spark period is there 216V D C across the pins at connector X2 Replace gas valve or check cable to it Yes No Yes TURN OFF GAS SUPPLY Remove the combustion chamber cover Is the sense right electrode and lead in good condition and is gap correct See Section 15 4 3 No Repair or replace flame sense or cable to it Replace control board Note It is not possible...

Страница 39: ...et to maximum Less than 75 C Such a fault is likely to be caused by one or more of the following Low gas pressure Partially blocked flue Partially blocked heat exchanger Blocked dirty burner Gas valve sticking Control board fault Faulty themister Replace control board Move control knob to lower setting Check thermister sensor heat conductive paste ...

Страница 40: ...nterests of continued improvement All goods sold are subject to our official Conditions of Sale a copy of which may be obtained on application PUBLICATION 8 716 103 192 a 09 01 Bosch Group Worcester Heat Systems Limited Cotswold Way Warndon Worcester WR4 9SW Telephone 01905 754624 Fax 01905 754619 Technical Helpline 08705 266241 www worcester bosch co uk ...

Страница 41: ...41 ...

Страница 42: ...1 49 50 9 14 CBi 41 311 50 51 28Si 47 311 51 52 14 19 CBi 41 311 52 53 C1 47 311 51 19 24 CBi 41 311 54 55 24CDi 47 311 30 31 WR325 52 311 02 28CDi 47 311 34 35 WH1 52 311 03 35CDi II 47 311 51 52 IMPORTANT THIS BOOKLET MUST BE READ FULLY IN CONJUNCTION WITH THE APPLIANCE INSTALLATION AND SERVICING INSTRUCTIONS THESE INSTRUCTIONS APPLY IN THE UK ONLY THESE INSTRUCTIONS ARE TO BE LEFT WITH THE USER...

Страница 43: ...able for installation in dwellings with pitched or flat roofs The minimum distance the Flue Terminal Assembly shall extend above the surface of the roof is 300mm This dimension is measured from the outside surface of a flat roof or the highest point on a pitched roof to the underside of the air inlet flange on the terminal assembly See Fig 2 Important All the Flue items referred to in this section...

Страница 44: ...ength to not exceed 800mm or 1550mm for 2 x 45 bends When measuring between the centre lines of flue ducts an allowance must be made for the relevant elbow Refer to Fig 3 Equivalent Length 4m 90 bends 0 5m 2m Equivalent length 2x750mm 1 5m 75mm MODEL 15SBi 79mm NONE NONE 24SBi EQUIVALENT FLUE LENGTHS UP TO 1M EQUIVALENT FLUE LENGTHS 1M TO 4M EQUIVALENT FLUE LENGTHS UP TO 725MM EQUIVALENT FLUE LENG...

Страница 45: ... top of the appliance then the flue adaptor is not required 3 5 FLUE SUPPORT Flue assembly lengths over 2000mm should be appropriately supported Refer to Fig 6 and Section 5 4 3 6 FIRE STOP SPACER The fire stop spacer is supplied with the flue kit Refer to Fig 7 and Section 5 3 3 7 ROOF FLASHING The roof flashing is not supplied This is available as a proprietary item Selkirk or similar from the b...

Страница 46: ... and pitched roofs Important The terminal assembly must extend at least 300mm above the surface or pitch of the roof The distance may vary depending upon the type of roof and surrounding structures In these instructions the distance is refered to as dimension F Refer to Fig 9 10 11 12 Fig 8 Marking out the flue assembly position Vertical Flue System no offset Appliance front Appliance front Vertic...

Страница 47: ...han 300mm Duct Length H 92mm Derivation Dimension G 1100 Fmm Dimension H E G Refer to 2 2 for maximum duct length 4 Measurement of Ducts Air inlet flange Weather sealing collar Secure with screw provided and seal with silicone sealant Roof flashing not supplied Flat roof Pitched roof Flue terminal assembly 106mm diameter Fire stop spacer Air and flue duct extension kits 750mm Vertical flue adaptor...

Страница 48: ...iameter marked on the inside surface of the roof Dimension K Refer to Fig 7 Note Dimension K for a pitched roof must go to the highest point of the hole diameter Determine dimension F Refer to Fig 1and 7 for the limiting figure Duct Length L 81mm Derivation Dimension G 1100 Fmm Dimension L K G Note The air duct must not be less than 100mm Air inlet flange Weather sealing collar Secure with screw p...

Страница 49: ...ide surface of the roof Dimension K Refer to Fig 6 and 7 Note Dimension K For a pitched roof must go to the highest point of the hole diameter Determine dimension F which must not be less than 300mm Duct Length L 81mm Dimension G 1100 F mm Dimension L K G Air inlet flange Weather sealing collar Secure with screw provided and seal with silicone sealant Roof flashing not supplied Flat roof Pitched r...

Страница 50: ...uts are square and free from burrs All dimensions refer to straight lengths and do not include the expanded ends Do not cut the expanded ends unless specifically instructed to do so 5 3 POSITION OF THE FIRE STOP SPACER ASSEMBLY Fit the fire stop spacer centrally over the hole in the ceiling Ensure the hole aligns with the flue spigot on top of the appliance casing 5 Installation of Flue Mark the f...

Страница 51: ...at each stage of the system assembly that each section is properly aligned Each air and flue duct joint must be sealed and fixed Each air and flue duct connection to an elbow must be sealed with silicone sealant and fixed with the screws provided Support any sections of the system until they are permanetely fixed into place using suitable support brackets 5 5 ASSEMBLY OF DUCTS 5 5 1 AIR DUCTS Chec...

Страница 52: ...s in the air duct Separate the assembly and apply silicone sealant to the outside of the air duct Re connect the assembly and fix with the screws provided Note The sealant and screws are not required for the flue duct Refer to Fig 13 5 10 SEAL THE TERMINAL ASSEMBLY TO THE ROOF From outside the building make good the roof structure and ensure the roof is weather sealed by fixing the roof flashing A...

Страница 53: ...interests of continued improvement All goods sold are subject to our official Conditions of Sale a copy of which may be obtained on application PUBLICATION 8 716 145 030d 08 01 Bosch Group Worcester Heat Systems Limited Cotswold Way Warndon Worcester WR4 9SW Telephone 01905 754624 Fax 01905 754619 Technical Helpline 0990 266241 www worcester bosch co uk ...

Отзывы: