Manual 35132
VariStroke-DX Duplex Hydraulic Servo Skid
Woodward
28
Unit Grounding
The junction box must be grounded using the designated PE ground connection point. PE ground
connection point is located on the sidewall of the junction box.
Figure 3-7. PE Ground Connection Localization and Details, Junction Box Version
In VS-DX with Junction Box version for the PE connection, use the required type wire (typically
green/yellow, 3 to 6 mm² / 12 to 10 AWG) as necessary to meet the installation safety ground requirements.
Torque the ground lug to 5.1 Nm (45 lb-in).
Figure 3-8. PE / Chassis Ground Connection Localization and Details,
Without Junction Box Version (On Both VS)
Released