ERRORS
When an error occurs, the valve closes, if possible. It
will not attempt to operate again until power to the
valve is cycled. If the error persists, the valve must
be replaced.
Error Description
Shutdown
One or more of the errors
below is active.
Internal Error
The valve has detected an
internal error that prevents it
from operating.
Delta P Sensor
High
The delta P sensor has failed
to a high value.
Delta P Sensor
Low
The delta P sensor has failed
to a low value.
Position Sensor
High
The position sensor has failed
to a high value.
Position Sensor
Low
The position sensor has failed
to a low value.
Position Error
The actuator was not able to
position the valve properly.