Manual 26185
TecJet 110 Fuel Metering System
Woodward
5
Installations with severe electromagnetic interference (EMI) may require
additional shielding precautions. Contact Woodward for more information.
Failure to provide shielding can produce future conditions which are difficult to
diagnose. Proper shielding at the time of installation is required to ensure
satisfactory operation of the TecJet 110 Gas Metering System.
CAN Hi In
CAN Lo In
CAN Shield
CAN Hi Out
CAN Lo Out
PWM In +
Keyswitch
Power In+
Power In -
TecJet 110
Jumper for CAN Termination
Resistor
Z
W
F
L
K
B
A
Q
P
U
T
X
S
R
PWM In -
4-20mA Analog In +
4-20mA Analog In -
}
}
From Previous
CAN Device
To Next CAN
Device
Battery
E
Status Output (Discrete)
M
J
Discrete/RS232 Common
RS232 Tx
V
CAN Gnd
Y
Do Not Connect
The recommended wire size for W and Z (Power Supply Inputs) is
at least 16AWG. For all other I/O the recommended wire size is
at least 20AWG.
N
RS232 Rx
Load
}
RS232 Serial
Communication
CAN ID2
CAN ID1
G
H
D
C
Do Not Connect
Do Not Connect
Figure 2-2. TecJet 110 Valve Wiring Diagram