Woodward
Manual MRM3-2 GB
48
TD_MRM3-2_09.08_GB_Rev.New
7.3.3 Load Unbalance Protection
Parameter LED
Setting
range
Notes Range
Step
Tolerance
Load unbalance
I2>
0,02...1,00
EXIT
Pick-up value nega-
tive phase sequence
system
- displayed in x I
N
- Step switched off
0.020 0.050
0.050 - 0.100
0.100 - 0.200
0.200 - 0.500
0.500 - 1.00
0.001
0.002
0.005
0.01
0.02
±
3% of setting
value
or
±
10mA
Characteristics I2>+CHA
R
DEFT
INVS
definite DMT
inverse IDMT
±
3% in relation
to the meas-
ured current
value or
±
30ms (see
EN 60255-3)
Time delay/
characteristic pa-
rameter
I2+t> At
DEFT:
1.00 ...600
Trip delay in s
1.0-5.0
5.0-10.0
10.0-20.0
20.0-50.0
50.0-100
100-200
200-600
0.1
0.2
0.5
1.0
2.0
5.0
10.0
±
3% of the set-
ting value or
±
25ms
at
INVS:
10.0 - 5000
EXIT
Characteristic
parameter
Warning only
10.0-20.0
20.0-50.0
50.0-100
100-200
200-500
500-1000
1000-2000
2000-5000
0.5
1.0
2.0
5.0
10
20
50
100
±
3% referring
to current
measuring
value or
±
30ms
(See EN
60255-3)