Manual 04121
ProAct I/II
Woodward
35
Menu 4—Limiter Settings
Menu Low
Default
High
Item
Value Value Value Units
Max Fuel Limit
0
100
100
%
Transient Over Fuel 0
0
100
%
Transient Time
0
0
10
seconds
Start Fuel Limit
0
40
100
%
Start Ramp Rate
0
1
20
%/second
Start Speed
0
400
1200
rpm
Min Torque Limit
0
50
100
%
Torque Limit BP
0
1500
2100
rpm
Torque Limit at BP
0
70
100
%
Max Torque Limit
0
90
100
%
Menu 5—Monitor Menu
Speed rpm
Speed Reference
rpm
Actuator Output
%
Aux Input
volts
Remote Input
mA
Run/Stop Switch
Open/Closed
Idle Rated Switch
Open/Closed
Raise Switch
Open/Closed
Lower Switch
Open/Closed
Alternate Dynamics Switch
Open/Closed
Remote Reference Switch
Open/Closed
Isoch Switch
Open/Closed
Diagnostic Switch
Open/Closed
Speed Switch A
On/Off
Speed Switch B
On/Off
Speed Switch C
On/Off
Fault Lamp
On/Off
Menu 6—Configuration Set Points
Menu Low
Default
High
Item
Value
Value Value Units
*Configuration Key
0
0
100
NA*
Number of Gear Teeth 4
60
500
NA
Dynamics Map
Linear
Linear
Nonlinear
NA
Failsafe Function
Disabled
Enabled
Enabled
NA
*—Must be set at "49" before any changes can be made. Engine must be at 0 rpm
and the Run/Stop at OPEN to make any changes in this menu.
The Failsafe Function must be enabled during normal engine
operation to prevent possible overspeed should the MPU signal be
lost for any reason. As soon as the control senses engine speed, the
failsafe becomes enabled. The function can be overridden to allow
some slow cranking engines to start, and to test parts of the
governor system without running the engine. Failure to enable the
Failsafe Function could allow overspeed with resulting damage to
equipment and possible personal injury or death.
Содержание ProAct I
Страница 10: ...ProAct I II Manual 04121 8 Woodward Figure 1 3 Example of ProAct II Actuator...
Страница 11: ...Manual 04121 ProAct I II Woodward 9 Figure 1 4 Outline Drawing of ProAct I or II Actuator...
Страница 12: ...ProAct I II Manual 04121 10 Woodward Figure 1 5 ProAct Wiring Diagram...
Страница 13: ...Manual 04121 ProAct I II Woodward 11 Figure 1 6 Outline Drawing of ProAct Control Box...
Страница 39: ...Manual 04121 ProAct I II Woodward 37 Figure 4 2 Typical Transient Response Curves...