Manual MRI3 GB
Woodward
DOK-TD-MRI3 Rev.A
39
Blockade function
Display
LED/Color
Blocking of the protection stage
PR_B
I>; I>>; I
E>
; I
E>>
Blocking of the trip function
TR_B
t
I>
; t
I>>
; t
IE>
; t
IE>>
I> Overcurrent NO_B
I>
yellow
I>>
Short circuit
BLOC
I>> yellow
I
E>
Earth current 1
st
element
NO_B
I
E>
yellow
I
E>>
Earth current 2
nd
element
NO_B
I
E>>
yellow
t
CBFP
Circui breaker failure protection
NO_B
CB green
Table 5.2: Default settings of both parameter sets
Assignment of the output relays:
Unit MRI3 has five output relays. The fifth output relay is provided as permanent alarm relay for self
supervision is normally on. Output relays 1 - 4 are normally off and can be assigned as alarm or
tripping relays to the current functions which can either be done by using the push buttons on the
front plate or via serial interface RS485. The assignment of the output relays is similar to the setting
of parameters, however, only in the assignment mode. The assignment mode can be reached only
via the blocking mode.
By pressing push button <SELECT/RESET> in blocking mode again, the assignment mode is se-
lected.
The relays are assigned as follows: LEDs I>, I>>, IE>, IE>> are two-colored and light up green
when the output relays are assigned as alarm relays and red as tripping relays.
In addition, the LED
→←
also lights up with each adjustment. Green means forward and red back-
ward direction.
Definition:
Alarm relays
are activated at pickup.
Tripping relays
are only activated after elapse of the tripping delay.
After the assignment mode has been activated, first LED I> lights up green. Now one or several of
the four output relays can be assigned to current element I> as alarm relays. At the same time the
selected alarm relays for frequency element 1 are indicated on the display. Indication "1_ _ _"
means that output relay 1 is assigned to this current element. When the display shows "_ _ _ _", no
alarm relay is assigned to this cur-rent element. The assignment of output relays 1 - 4 to the cur-
rent elements can be changed by pressing <+> and <-> push buttons. The selected assignment
can be stored by pressing push button <ENTER> and subsequent input of the password. By press-
ing push button <SELECT/RESET>, LED I> lights up red. The output re-lays can now be assigned
to this current element as tripping relays.
Relays 1 - 4 are selected in the same way as described before. By repeatedly pressing of the
<SELECT/RESET> push button and assignment of the relays all elements can be assigned sepa-
rately to the relays. The assignment mode can be terminated at any time by pressing the
<SELECT/RESET> push button for some time (abt. 3 s).
Note:
The function of jumper J2 described in general description "MR Digital Multifunctional
Relays" has no function. For relays without assignment mode this jumper is used for
parameter setting of alarm relays (activation at pickup or tripping).
A form is attached to this description where the set-ting requested by the customer can be
filled-in. This form is prepared for fax transmission and can be used for your own reference
as well as for telephone queries.