5.4.10 WARN/TRIP changeover (all earth fault-relay type)
A detected earth fault can be parameterized as follows. After delay time.
a) "warn" only the alarm relay trips
b) "trip" the trip relay trips and tripping values are stored.
5.4.11 Time current characteristics for earth fault element (CHAR I
E
) (not for
ER/XR-relay type)
By setting this parameter, one of the following 7 messages appears on the display:
DEFT -
Definite Time (independent overcurrent
time
protection)
NINV -
Normal inverse (Type A)
VINV -
Very inverse (Type B)
EINV -
Extremely inverse (Type C)
RINV
RI-Inverse
LINV
Long Time Inverse
RXID
Special
characteristic
Anyone of these four characteristics can be chosen by using <+> <->-pushbuttons, and can be
stored by using <ENTER>-pushbutton.
5.4.12 Trip delay or time multiplier for earth fault element (t
IE>>
)
(Similar to chapter 5.4.3)
5.4.13 Reset mode for inverse time tripping in earth current path
(Similar to chapter 5.4.4)
5.4.14 Current setting for high set element of earth fault supervision (I
E>>
)
(Similar to chapter 5.4.5)
The pickup value of YR, X and XR-relay type relates to % I
N
.
5.4.15 Trip delay for high set element of earth fault supervision (t
IE>>
)
(Similar to chapter 5.4.6)
5.4.16 COS/SIN Measurement (ER/XR-relay type)
Depending on the neutral earthing connection of the protected system the directional element of
the earth fault relay must be preset to cos
φ
or sin
φ
measurement.
By pressing <SELECT> the display shows "COS" resp. "SIN". The desired measuring principle can
be selected by <+> or <-> and must be entered with password.