Manual MRI3-ITER GB
Woodward
DOK-TD-MRI3 ITERE Rev.A
23
5. Operation and settings
5.1 Display
Function
Display shows
Pressed pushbutton
Corresponding
LED
Normal operation
SEG
Measured operating values
actual measured val-
ues, related to I
N
,
Temperature equivalent
in %
<SELECT/RESET>
one time for each value
L1, L2, L3, E
A
,
T
, I
P
, I
Q
Measuring range overflow
max.
<SELECT/RESET>
A
und
T
Display of the second rated repetition
current
SEC 0.002-50.0
kA=prim
<+> <-><SELECT/RESET> L1, L2, L3, E
Rated frequency
f = 50 / f = 60
<+> <-><SELECT/RESET>
LED-blinking after activation
FLSH/NOFL
<+> <-><SELECT/RESET>
Parameter switch/external trigger-
ing of the fault recorder
SET1, SET2, B_S2,
R_S2, B_FR, R_FR,
S2_FR
<+> <-><SELECT/RESET> P2
Constant k
Factor for pickup cur-
rent
<+> <-><SELECT/RESET> k
A
and k
T
Time constant
Cooling time/warming
up time constant
<+> <-><SELECT/RESET>
C
and
W
Blocking of function
EXIT
<+> until max. setting
value
LED of blocked
parameter
Characteristics DEFT,NINV,
VINV,
EINV, LINV, RINV,
<+> <-><SELECT/RESET>
CHAR I>
Characteristics
DEFT, NINV, VINV,
EINV, LINV, RINV
<+> <-><SELECT/RESET> CHAR IE>
Switch failure protection
CBFP
after tripping
C. B.
Recorded fault data
Phase currents, earth
currents and tempera-
ture equivalent
<SELECT/RESET>
one time for each phase
L1, L2, L3, E
A
and
T
Enquiry failure memory
FLT1, FLT2..... <+>
<-><SELECT/RESET> L1, L2, L3, E
I>, I>>, I
E>
, I
E>>
,
Delete failure memory
wait <+>
<-><SELECT/RESET>
Relay trip
TRIP
<TRIP> or after fault trip-
ping
Secret password input
„XXXX“
<+><-> <ENTER>
<SELECT/RESET>
System reset
SEG
<SELECT/RESET>
for about 3 s
Manual trip
TRI?
<TRIP> three times
Inquire password
PSW?
<TRIP><ENTER>
Blocking of protection function
BLOC, NO_B
<ENTER> und <TRIP>
Change over the blockage function
²
)
PR_B, TR_B
<ENTER> und <TRIP>;
<+><->
I>, I>>, I
E>
, I
E>>
,
oder t
I>
, tI>>, t
IE>
,
t
IE>>
Relay assignment
e. g. _ 2 _ _
<ENTER> and <TRIP>
Trigger signal for the fault recorder P_UP; A_PI; TRIP;
TEST
<+> <-><SELECT/RESET> FR
Number of fault occurences
S = 2, S = 4, S = 8
<+> <-><SELECT/RESET> FR
Display of date and time
Y = 99, M = 10, D = 1,
h = 12, m = 2, s = 12
<+> <-><SELECT/RESET>
Slave address of serial interface
1-32
<+> <-><SELECT/RESET> RS
Baud-Rate
1)
1200-9600
<SELECT/RESET>
<+><->
RS
Parity-Check
1)
even odd no
<SELECT/RESET> <+><-> RS
Parameter switch
SET1; SET2 <+>
<-><SELECT/RESET>
P2
Setting values:
Currents and time delays
Current and time
settings
<SELECT/RESET>
one time for each
parameter
I
B,A
; I
B,T
; k
A
; k
T
;
I>; CHAR I>; t
I>
;
I>>;
t
I>>
;
I
E>
; CHAR I
E>
;
t
IE>
; I
E>>
;