Woodward 

Manual MRI3-ITER GB 

28 

DOK-TD-MRI3 ITERE Rev.A 

5.3.5 Nominal 

frequency 

 
The adapted FFT-algorithm requires the nominal frequency as a parameter for correct digital  
sampling and filtering of the input currents. 
By pressing <SELECT> the display shows "f=50" or "f=60". The desired nominal frequency can be 
adjusted by <+> or <-> and then stored with <ENTER>. 
 

5.3.6  Display of the activation storage (FLSH/NOFL) 

 
If after an activation the existing current drops again below the pickup value, e.g. I>, without a trip 
has been initiated, LED I> signals that an activation has occurred by flashing fast. The LED keeps 
flashing until it is reset again (push button <RESET>). Flashing can be suppressed when the pa-
rameter is set to NOFL. 
  

5.3.7  Parameter switch/external triggering of the fault recorder 

 
By means of the parameter-change-over switches it is possible to activate two different parameter 
sets. Switching over of the parameter sets can either be done by means of software or via the  
external inputs RESET or blocking input. Alternatively, the external inputs can be used for Reset or 
blocking of the triggering of the fault recorder. 
 

Software-
parameter 

Blocking input used as 

RESET input used as 

SET1 

Blocking input 

RESET input 

SET2 

Blocking input 

RESET input 

B_S2 

Parameter switch 

RESET input 

R_S2 

Blocking input 

Parameter switch 

B_FR 

External triggering of the fault re-
corder 

RESET input 

R_FR 

Blocking input 

External triggering of the fault recorder 

S2_FR 

Parameter switch 

External triggering of the fault recorder 

 
With the settings SET1 or SET2 the parameter set is activated by software. Terminals C8/D8 and 
D8/E8 are then available as external reset input or blocking input. 
 
With the setting B_S2 the blocking input (D8, E8) is used as parameter-set change-over switch. 
With the setting R_S2 the reset input (D8, E8) is used as parameter-set changeover switch. With 
the set-ting B_FR the fault recorder is activated immediately by using the blocking input. On the 
front plate the LED FR will then light up for the duration of the recording. With the setting R_FR the 
fault recorder is activated via the reset input. With the setting S2_FR parameter set 2 can be acti-
vated via the blocking input and/or the fault recorder via the reset input. 
 
The relevant function is then activated by applying the auxiliary voltage to one of the external in-
puts. 
 

Important note: 

When functioning as parameter change over facility, the external input RESET is not available for 
resetting. When using the external input BLOCKING the protection functions must be deactivated 
by software blocking separately (refer to chapter 5.7.1). 
 

 

Содержание MRI3-ITE

Страница 1: ...MRI3 ITE R Time overcurrent relay with thermal replica and earth current measuring Manual MRI3 ITER Revision A...

Страница 2: ...serves the right to update any portion of this publication at any time Information provided by Woodward Governor Company is believed to be correct and reliable However no responsibility is as sumed by...

Страница 3: ...5 3 7 Parameter switch external triggering of the fault recorder 28 5 4 Protection parameters 29 5 4 1 Pickup value of the thermal overload protection IB A and IB T 29 5 4 2 Constant k 29 5 4 3 Energi...

Страница 4: ...TE 41 6 4 3 Checking the input circuits and measured values 41 6 4 4 Example of a test circuit with earth fault directional feature 42 6 4 5 Checking the operating and resetting values of the relay 43...

Страница 5: ...tected taking into account its initial load The MRI3 ITE R furthermore provides a universal time over current and earth fault protection with the following functions Integrated determination of earth...

Страница 6: ...nt inverse time and definite time over current relay both for phase and earth faults determination of earth short circuit fault direction for systems with isolated or compensated neutral point Display...

Страница 7: ...onnections Figure 3 1 Connection diagram Figure 3 2 Phase current measuring and earth current detection by means of Holmgreen circuit This connection can be used with three existing phase current tran...

Страница 8: ...ctional detection Figure 3 4 Measuring of the phase voltages for the directional detection at earth fault protection IE and IE 3 1 1 Analogue input circuits The protection unit receives the analogue i...

Страница 9: ...arm Apart from the relay for self supervision all protective functions can be op tionally assigned Relay 1 C1 D1 E1 and C2 D2 E2 Relay 2 C3 D3 E3 and C4 D4 E4 Relay 3 C5 D5 E5 Relay 4 C6 D6 E6 Relay 5...

Страница 10: ...havior of the fault recorder can be influenced No writing over If 2 4 or 8 recordings are chosen the complete memory is divided into the relevant number of partial segments If this max number of fault...

Страница 11: ...ch memory segment has a specified storage time which permits setting of a time prior to the trigger event Via the interface RS485 the data can be read and processed by means of a PC with HTL PL Soft4...

Страница 12: ...Woodward Manual MRI3 ITER GB 12 DOK TD MRI3 ITERE Rev A 3 3 Front plate Figure 3 8 Front plate MRI3 ITE Figure 3 9 Front plate MRI3 ITER...

Страница 13: ...t to the alphanumerical display light up green during mea suring and red at alarm LEDs underneath the pushbutton SELECT RESET light up green during setting and inquiry of the setting values printed le...

Страница 14: ...le Read Only Memory With this program the CPU of the microcontroller calculates the three phase in order to detect a possible fault situation in the protected object For the calculation of the current...

Страница 15: ...e temperature according to which the object to be protected reaches its tripping value after expiry of a long time Trip k2 100 Adjustment of the nominal current with IB e g 1 IN and selection of an ov...

Страница 16: ...pickup value in the MRI3 ITE is deter mined by IB the following relation is effective n k IB k For this purpose the temperature T that really prevails in the electrical equipment needs to be known Th...

Страница 17: ...ulate the thermal equivalent n The last value n 1 the stationary final value max for the actual current the adjusted time constant and the time since the last calculation dt must be known Analogous fo...

Страница 18: ...d current and the actual current the cooling down or warming up constant will be applied for calculation In In 1 warming up In In 1 cooling down If the relay is supplied by the mains to be protected i...

Страница 19: ...ansformers supplying the relay Earth faults beyond the current transformers i e on the consumer or line side will not be detected Figure 4 4 Generator stator earth fault protection 4 5 2 System earth...

Страница 20: ...idual voltage UE required for determining earth fault direction can be measured in three different ways depending on the voltage transformer connections refer to Table 4 1 Total current can be measure...

Страница 21: ...ltage UE the ER XR relay type determines whether the line to be protected is earth faulted On non earth faulted lines the capacitive component Ic a of the total current precedes the residual voltage b...

Страница 22: ...which for instance are caused an electric arc fault do not impair the protective function 4 7 Demand imposed on the main current transformers The current transformers have to be rated in such a way th...

Страница 23: ...Switch failure protection CBFP after tripping C B Recorded fault data Phase currents earth currents and tempera ture equivalent SELECT RESET one time for each phase L1 L2 L3 E A and T Enquiry failure...

Страница 24: ...IE Save parameter SAV ENTER Save parameter SAV ENTER for about 3 s Display of software version First part e g D21 Second part e g 1 00 TRIP one time for each part Setting of the transformer connec tio...

Страница 25: ...erload low set element reached T Tripping at k 2 100 red continuously Temperature limit of trip element reached IB A Setting green continuously Setting switch point kA Setting red continuously Define...

Страница 26: ...ripping red continuously IE tripped IE Setting green continuously Setting switching point IE tIE Setting red continuously Setting time delay tIE IE tIE Pickup red flashing Pickup of IE IE tIE Tripping...

Страница 27: ...nt is 1380 A The parameter is set to 1500 A and on the display 1380 A are shown If the parameter is set to sec the value shown on the display is 0 92 x In Note The pick up value is set to a multiple o...

Страница 28: ...ut RESET input SET2 Blocking input RESET input B_S2 Parameter switch RESET input R_S2 Blocking input Parameter switch B_FR External triggering of the fault re corder RESET input R_FR Blocking input Ex...

Страница 29: ...tion of the thermal overload k IB might be exceeded for a short time The warning relay responds and the LEDs indicate energizing This excitation signal remains activated even after completion of the...

Страница 30: ...he flashing LED the relay will be set to the most sensitive time setting value of the selected characte ristics after five minutes warning of flashing LED tI The most sensitive time setting value mean...

Страница 31: ...acteristics for earth fault element CHAR IE not ER device type By setting this parameter one of the following 7 messages appears on the display DEFT Definite Time independent over current time protect...

Страница 32: ...blocked refer to Chapter 5 7 1 5 4 21 Circuit breaker failure protection tCBFP The CB failure protection is based on supervision of phase currents during tripping events Only af ter tripping this prot...

Страница 33: ...ge is initiated after recognition of a general activation TRIP Storage is initiated after a trip has occurred A_PI After Pickup Storage is initiated after the last activation threshold was fallen shor...

Страница 34: ...ed or TR_B the tripping stages are blocked The settings can be changed by actuating the keys or In this procedure the LEDs I I IE IE are simultaneously alight in case of protective blocking PR_B and L...

Страница 35: ...or several of the four output relays can be assigned to element I as alarm relays At the same time the selected alarm relays for element I are indicated on the display Indication 1_ _ _ means that ou...

Страница 36: ..._ I green tI Trip X 1 _ _ _ tI green I Alarm X _ _ 3 _ I green tI Trip X 1 _ _ _ tI green IE V Alarm X _ _ _ 4 IE green tIE V Trip X 1 _ _ _ tIE green IE R Alarm X _ _ _ 4 IE redt tIE R Trip X 1 _ _...

Страница 37: ...ctive earth current LED E and IQ green Residual voltage UE LED UE only at ITER relay type Angle between IE and UE only at ITER relay type 5 8 2 Unit of the measuring values displayed The measuring val...

Страница 38: ...sed during normal measuring value indication Normal measuring values are selected by pressing the SELECT RESET button When then the button is pressed the latest fault data set is shown By repeated pre...

Страница 39: ...as the SELECT RESET pushbutton see also communication protocol of RS485 interface The display can only be reset when the pickup is not present anymore otherwise TRIP remains in display During resettin...

Страница 40: ...the relay e g D21 By pressing the pushbutton TRIP twice the display shows the second part of the software version of the relay e g 1 00 The software version should be quoted in all correspondence Pres...

Страница 41: ...en parameter Iprim s is set the indication is 0 2 x In and at 5 the indication is 1 00 A The current can be also injected into the other current input circuits Phase 2 terminals B5 B6 Phase 3 terminal...

Страница 42: ...arameter Voltage transformer connection for residual voltage measuring refer to 5 3 4 must be adjusted to 3Pha The appropriate measuring value is selected via the SELECT RESET key The display must in...

Страница 43: ...ction test the test current must be very stable Oth erwise the test results may be wrong This especially applies for currents smaller than 2 x IS where the trip delays are in the steep range of the in...

Страница 44: ...certained by the timer should not deviate more than 1 or at short trip delay less than 10 ms from the set tripping time Alternatively the timer can be started when the aux voltage and the test current...

Страница 45: ...be substantially longer This is because The MRI3 ITER relays are equipped with very wide self supervision functions so that many faults in the relay can be detected and signalized during service Impo...

Страница 46: ...pout to pickup ratio for phase current in range 0 2 x IN to 0 5 x IN 100 Returning time 30 ms Time lag error class index E 10 ms Minimum operating time 60 ms Transient overreach at instantaneous opera...

Страница 47: ...002 0 200 0 002 kA 0 200 0 500 0 005 kA 0 500 1 00 0 01 kA 1 00 2 00 0 02 kA 2 00 5 00 0 05 kA 5 00 10 0 0 1 kA 10 0 20 0 0 2 kA 20 0 50 0 Ue Uprim Usek SEK 1 01 6500 0 01 1 01 2 00 0 02 2 00 5 00 0 0...

Страница 48: ...50 100 10 0 100 260 3 resp 20 ms IB TRIP 0 4 3 5 x IN EXIT 0 02 x IN 0 4 1 0 0 05 x IN 1 0 3 5 3 from set value or 2 5 IN kT 0 5 5 0 01 0 5 1 0 0 02 1 0 2 0 0 05 2 0 5 0 IB Trip 0 04 260 s EXIT defin...

Страница 49: ...02 0 04 1 0 0 05 1 0 2 0 0 1 2 0 5 0 0 2 5 0 8 5 0 5 8 5 10 0 1 0 10 20 2 0 20 50 5 0 50 100 10 0 100 260 0 01 0 05 0 5 0 02 0 5 1 0 0 05 1 0 2 0 0 1 2 0 5 0 0 2 5 0 10 0 0 5 10 0 20 0 3 or 20 ms 5 f...

Страница 50: ...1 0 2 0 0 1 2 0 5 0 0 2 5 0 10 0 0 5 10 0 20 0 3 or 20 ms 5 for NINV and VINV 7 5 for NINV and EINV IE 0 01 2 0 x IN EXIT E 0 01 0 45 x IN EXIT ER 0 001 0 01 0 05 0 002 0 05 0 1 0 005 0 1 0 2 0 01 0 2...

Страница 51: ...Trip 0 1 2 0 s EXIT 0 01 0 02 0 05 0 1 s 1 bzw 10 ms 7 3 8 Switch failure protection tCBFP 0 1 2 0 s EXIT 0 01 0 02 0 05 0 1 s 1 bzw 10 ms 7 3 9 Interface parameter only Modbus Protocol 7 3 10 Parame...

Страница 52: ...ing is realized as soon as the temperature equivalent k2 100 is reached This tempera ture equivalent equals a permanent load current of k IB Trip k2 100 Trip k2 100 For the tripping characteristic 100...

Страница 53: ...B Woodward DOK TD MRI3 ITERE Rev A 53 7 4 2 Preload factor The normal tripping characteristic according to IEC 255 8 In I IB p l lB k Figure 7 1 Tripping characteristics for various preload factors p...

Страница 54: ...ding to IEC 255 4 or BS 142 Normal Inverse type A 0 14 1 Very Inverse type B 13 5 1 Extremely Inverse type C 80 1 Long time inverse 120 1 RI inverse 1 0 339 0 236 RXIDG characteristic 5 8 1 35 Where t...

Страница 55: ...igure 7 2 Normal Inverse Figure 7 3 Very Inverse 1 2 3 4 5 6 7 8 910 20 I IS 0 1 1 10 100 1000 t s tI 0 05 0 1 0 2 0 3 0 4 0 5 0 6 0 8 1 0 1 4 2 0 3 0 4 0 6 0 8 0 10 0 1 2 3 4 5 6 7 8 910 20 I IS 0 1...

Страница 56: ...7 5 Definite time over current relay 1 2 3 4 5 6 7 8 910 20 I IS 0 01 0 1 1 10 100 1000 t s tI 0 05 0 05 0 1 0 1 0 2 0 3 0 4 0 5 0 6 0 8 1 0 10 0 1 4 2 0 3 0 4 0 6 0 8 0 1 10 I IN 0 01 0 1 1 10 100 t...

Страница 57: ...se Figure 7 7 RXIDG characteristic 1 2 3 4 5 6 7 8 910 20 I IS 0 1 1 10 100 1000 10000 t s tI 1 0 2 0 10 0 8 0 6 0 5 0 4 0 3 0 0 8 0 6 0 5 0 4 0 3 0 2 0 1 0 05 1 2 3 4 5 6 7 8 910 20 I IS 0 1 1 10 100...

Страница 58: ...e 7 6 Output relays Contacts 2 change over contacts for relay 1 and 2 1 change over contact for relay 3 4 Technical data subject to change without notice 1 2 3 4 5 6 7 8 910 20 I IS 0 1 1 10 100 t s t...

Страница 59: ...rmal replica MRI3 T 3 phase current I I Rated current 1 A 5 A I1 I5 Thermal replica Earth current none Rated current 1 A 5 A E1 E5 Directional feature in earth path none Rated voltage 100 V in earth p...

Страница 60: ...te and should the occasion arise adjusted to the object item to be protected Setting of parameters System parameter MRI3 Function Unit type MRI3 IT ITE ITER Default Actual setting setting L1 L2 L3 Ipr...

Страница 61: ...ase overcurrent element s X X X 0 06 I CHARI Reset Modus X X X I Pickup value for overcurrent high set element x IN X X X 1 00 tI Trip delay for overcurrent high set element s X X X 0 06 1 1 3pha e n...

Страница 62: ...ng No blocking Parameter set Set 1 Set 2 Set 1 Set 2 Set 1 Set 2 Set 1 Set 2 I X X I X X IE X X IE X X tCBFP X X Assignment of the output relays Function Relay 1 Relay 2 Relay 3 Relay 4 Default settin...

Страница 63: ...e Minute m 00 Setting of the second Second s 00 Setting of code jumpers Code jumper J1 J2 J3 Default set ting Actual set ting Default set ting Actual set ting Default set ting Actual setting Plugged N...

Страница 64: ...pen Germany Postfach 10 07 55 P O Box D 47884 Kempen Germany Phone 49 0 21 52 145 1 Internet www woodward com Sales Phone 49 0 21 52 145 216 or 342 Telefax 49 0 21 52 145 354 e mail salesEMEA_PGD wood...

Отзывы: