Measurement Value Logging
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
Voltage
Voltage is displayed as three-phase r.m.s measurement of the phase-neutral and/or phase-phase voltages.
Op-
tion YC
utilizes single-phase r.m.s. measurement of the synchronizing voltage V
L1-L2
.
This device can be ordered with the following measuring voltage input ranges (rated voltages). Please indi-
cate the measuring voltage input required when ordering (refer to Technical Data on page 60):
•
66 V/115 V .................... [1]
•
230 V/400 V .................... [4]
•
400 V/690 V .................... [7]
Frequency
Frequency measurement is extracted from the digitally filtered measuring voltages. The frequency is meas-
ured three-phase if the measured voltage exceeds 15% of the nominal voltage. This ensures rapid and precise
measurement of the frequency. However the frequency is still measured correctly even if voltage is only ap-
plied to one phase.
NOTE
This manual has been developed for a unit fitted with all available options. Inputs/outputs, functions,
configuration screens, and other details described, which do not exist on your unit, may be ignored.
The present manual has been prepared to enable the installation and commissioning of the unit. Due to
the large variety of parameter settings, it is not possible to cover every combination. The manual is
therefore only a guide. In case of incorrect entries or a total loss of functions, the default settings may
be taken from the list of parameters enclosed at the rear of this manual.