2.3
G99-Specific LoM Protection Settings
For Loss of Mains (ROCOF, Intertripping), the G99-type-tested variant of the MRU4
features the following settings:
• Intertripping is enabled by default, as it is expected for the
, but can be
disabled.
• »df/dt« (ROCOF) is enabled by default in the [Device planning] menu, as it is
The threshold and delay times are fixed according to the EREC G99‑1‑6
requirements.
2.3.1
Intertripping
Intertripping . Mode
[Device planning]
use
Intertripping Module, general operation mode:
This is enabled by default, but can be disabled.
For the password-protection (of access level
“S.3”), see the “Security” chapter in the generic
MRU4 User Manual.
S.3
Intertripping . Function
[Protection Para / Set 1…4 / Intercon-Prot / Mains
Decouplg / Intertripping]
• Set 1: inactive
• Set 2: inactive
• Set 3: inactive
• Set 4: inactive
Permanent activation or deactivation of Intertripping:
This module is inactive by default, because the factory-
preset enables the
HV protection, and
Intertripping is expected only for
For a Type D application, set this to active.
For the password-protection (of access level “P.2”), see
the “Security” chapter in the generic MRU4 User
Manual.
P.2
21
MRU4
MRU4-3.6-EN-G99
2 G99-Specific Protection Settings
2.3 G99-Specific LoM Protection Settings