2.1.6
V[6]: Voltage Protection Pre-Configured According to the HV
Requirements
V[6] . Mode
[Device planning]
V>
Voltage protection instance number 6: Pre-configured
as overvoltage protection for HV connections.
For the password-protection (of access level “S.3”), see
the “Security” chapter in the generic MRU4 User
Manual.
S.3
V[6] . Function
[Protection Para / Set 1…4 / V-Prot / V[6]]
• Set 1: active
• Set 2: active
• Set 3: active
• Set 4: active
Permanent activation or deactivation of module/stage:
This instance V[6] is pre-configured for HV
applications.
It is active by default. This means that if you need to
switch to LV protection, you have to make the following
settings:
• »V[1] . Function« = “active”,
and the same for »V[2]«, »V[3]«
• »V[4] . Function« = “inactive”,
and the same for »V[5]«, »V[6]«
Furthermore, this stage is optional for
applications and may be set to inactive for these.
For the password-protection (of access level “P.2”), see
the “Security” chapter in the generic MRU4 User
Manual.
P.2
V[6] . Measuring Mode
[Protection Para / Set 1…4 / V-Prot / V[6]]
• Set 1: Phase to Phase
• Set 2: Phase to Phase
• Set 3: Phase to Phase
• Set 4: Phase to Phase
Measuring/Supervision Mode: Determines if the phase-
to-phase or phase-to-earth voltages are to be
supervised.
For the password-protection (of access level “P.2”), see
the “Security” chapter in the generic MRU4 User
Manual.
P.2
16
MRU4
MRU4-3.6-EN-G99
2 G99-Specific Protection Settings
2.1.6 V[6]: Voltage Protection Pre-Configured According to the HV Requirements