background image

Manual 37138C 

ESDR 4T - Current Differential Protection Relay 

 

 

 

 

Page 18/46 

© Woodward 

Electrical Restraint of Inrush Current and Overexcitation with Transformers 

Certain transformer operational conditions can cause differential currents without there actually being a fault pre-
sent at the protected object. This includes energizing the transformer and operating in overexcitation mode. 
When a transformer is energized, a current inrush flows in on one side which can be variably high depending on 
the instantaneous value of the supply current. If a long high-voltage line has a transformer at the end that is being 
energized, overvoltages can occur and overexcite the transformer, inducing increased currents on one side. As 
the currents only flow one-sided in both cases, a differential current will be measured which results in false trip-
ping. 
 
During an inrush current there are typically high proportions of 2nd order harmonics present. However during 
overexcitation there are predominantly 5th order harmonics present. The harmonics component is determined in 
the ESDR 4T using the digital Fourier transformation (= DFT) and this is used as the criteria for electrical re-
straint against false tripping. 
 
To activate the electrical restraint of an inrush current or an overexcitation, enable the "Stabilization Rush" func-
tion in the configuration mode by configuring as ON and set an operate margin in the next screen. The operate 
margin must be set for rush detection. This limit must be set so that it is not exceeded in normal operation. But it 
must be exceeded if an inrush current occurs. The proportion of 2

nd

 harmonics in normal operation and in the 

starting current depends in part on the type of transformer construction and the starting torque. As such, no gen-
eral operate margin can be given here. The documentation contains notes stating that the proportion of 2

nd

 order 

harmonics when there is inrush current is always over 50 % and always under 30 % when there is a short-circuit. 
Only step  1 of the differential current tripping can be stabilized; step 2 causes constant tripping. When electrical 
restraint is activated you should ensure that the time lag for monitoring the differential current 1 is at least 
0.08 seconds. 

Self-Monitoring 

≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡

 

 
The unit is equipped with an operational readiness message for self-monitoring. It is available externally via a 
contact assembly. The ready for operation signal is disabled if the unit's supply voltage drops below approxi-
mately 19 Vdc or if there is an internal malfunction. 

Configuration 

≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡

 

 
The operating parameters may be entered in through the buttons on the front panel. To change these parameters, 
the control must be in the configuration mode. The control unit will continue to operate while in the configura-
tion mode. This may result in the control unit accidentally issuing a breaker open command if the parameters are 
changed while in the operation mode. 
 

Содержание ESDR 4T

Страница 1: ...37138C ESDR 4T Current Differential Protection Relay Manual Manual 37138C...

Страница 2: ...e disconnecting the battery from the system Electronic controls contain static sensitive parts Observe the following precautions to prevent dam age to these parts Discharge body static before handling...

Страница 3: ...L DESCRIPTION 14 Introduction 14 Measurement Inputs 15 Differential Current Monitoring 16 Tripping Characteristic 16 Electrical Restraint of Inrush Current and Overexcitation with Transformers 18 Self...

Страница 4: ...X C LIST OF PARAMETERS 39 APPENDIX A SERVICE OPTIONS 41 Product Service Options 41 Returning Equipment for Repair 41 Packing a Control 42 Return Authorization Number RAN 42 Replacement Parts 42 How to...

Страница 5: ...s the differential current and re straint current internally for each phase separately The following settings are taken into account for this Transformer vector group Rated current of the protection o...

Страница 6: ...unit fitted with all available options Inputs outputs functions configuration screens and other details described which do not exist on your unit may be ignored The present manual has been prepared to...

Страница 7: ...cup holders cigarette packages cellophane wrappers vinyl books or folders plastic bottles and plastic ash trays away from the control the modules and the work area as much as possible 4 Opening the co...

Страница 8: ...nected to the system such as operating current coils undervoltage tripping units or auxiliary power contacts must be connected to a suitable interference suppressor The following chart may be used to...

Страница 9: ...8 29 T G Transducer set 2 low votlage side 36 33 34 31 32 18 Acknowledgement Relay 1 Relay 2 Relay 3 Ready for operation Relay 4 0 Vdc 24 Vdc Common Configuration off 6 1 2 3 4 5 2003 07 14 ESDR 4T Wi...

Страница 10: ...T Current Differential Protection Relay Page 10 46 Woodward Power Supply 24 Vdc 25 13 14 24 Vdc 0 V Power supply Figure 3 2 Power supply Terminal Description Amax 13 24 V DC 10 W 2 5 mm 14 0 Vdc refer...

Страница 11: ...et 2 L2 L1 L3 G l s2 k s1 L2 l s2 k s1 l s2 k s1 l s2 k s1 L3 L2 L1 l s2 k s1 l s2 k s1 25 26 30 29 28 27 35 36 33 34 31 32 L1 L3 Generator diff prot G Protection object Figure 3 3 CT transducer input...

Страница 12: ...e Signal device Signal device Blocking Acknowledgment Configuration 18 to 250 V ac dc 17 15 18 15 19 15 Figure 3 4 Discrete inputs Terminal Associated common Description according to DIN 40 719 sectio...

Страница 13: ...rnal device external device C D E Relay output external device external device F G H Figure 3 5 Relay outputs Terminal Amax Root Make contact A B Description 7 8 Relay 3 Ready for operation 2 5 mm Mak...

Страница 14: ...ng settings are taken into account for this Transformer vector group Rated current of the protection object on the low voltage side Rated primary current of the current transformer on the high and low...

Страница 15: ...nal short circuit In order to prevent a tripping of the relay due to spurious currents the trigger threshold is not held statically constant but increases in relation to the restraint cur rent Is Spur...

Страница 16: ...via the discrete input terminal 18 Reset Tripping Characteristic The following figure shows the tripping and warning characteristics with sample values for X12 Y1 and Y2 It represents the tripping an...

Страница 17: ...ject 100 200 Characteristic gradient fixed 10 Monitoring step 2 fixed limit 100 X12 Y2 and Y1 adjustable N I 100 P X12 Y2 P X12 Y1 Y I d a I 300 400 2004 02 12 ESDR 4 Characteristic e4ww 0704 kenn skf...

Страница 18: ...figuring as ON and set an operate margin in the next screen The operate margin must be set for rush detection This limit must be set so that it is not exceeded in normal operation But it must be excee...

Страница 19: ...and text is not dis played Relays Relay 1 Terminals 1 2 3 The function of this relay may be configured Refer to Configuring the Relay on page 25 for details Relay 2 Terminals 4 5 6 The function of th...

Страница 20: ...onitoring Differential Current Protection ON Alarm Is Ia Ib 2 Ia Ib Id Protected Object Ia Ib Operating and Alarm Messages L1 L2 L3 Release Variable Release Characteristic X Y 10 Id N I Is N I Lock Is...

Страница 21: ...o the other If the digital input terminal 17 Configuration off is energized the display changes into Display mode and can not be changed to configuration mode If this digital input will be de energize...

Страница 22: ...vert to the lowest permissible number 14 Clear Cursor Clear Cursor Display mode Clear The alarm text in the LC display is deleted if this button is pressed and held for 3 seconds and no alarm condi ti...

Страница 23: ...nitoring level 2 L1 Idiff 2 Id In Differential current in Phase L2 exceeds the rated current monitoring level 2 L2 Idiff 2 Id In Differential current in Phase L3 exceeds the rated current monitoring l...

Страница 24: ...utomatically revert into Display mode During the configuration mode the monitoring function is still enabled This means inevitably that while adjust ing parameters during operation it is possible to c...

Страница 25: ...n the correctness of the code Correct codeIf the code for the active seal has been entered correctly the follow ing screens are skipped and the user may proceed to configure the pa rameters The defaul...

Страница 26: ...n Relay Page 26 46 Woodward Code no 000 Breake Code no 001 New code Adjust settings ANWAHL SELECT Code no 000 Code SEALING Wrong Code ANWAHL SELECT Sealing ON OFF Code O K NO JA To leave the sealing p...

Страница 27: ...e subsequent screens are not displayed Funct rel 12 R releases AA Funct rel 34 R releases RA Relays 1 2 3 and 4 functions A R A choice is made between different control principles with the selection o...

Страница 28: ...s to the relays 1 to 4 The number of the relay to be enabled when the respective set point is exceeded has to be configured If left as all 0s no message will be issued It does not matter what order th...

Страница 29: ...the transformer s capacity when at maximum current A smaller current transformer ratio would cause inaccuracies in the monitoring functions Curr transf Id low vol 0000A Primary value low voltage side...

Страница 30: ...arrangement LV Z circuit arrangement 0 Yd11 HV circuit arrangement LV circuit arrangement 11 30 330 Yy6 HV circuit arrangement LV circuit arrangement 6 30 180 Dy11 HV circuit arrangement LV circuit a...

Страница 31: ...onds when electrical restraint of inrush current or over excita tion is activated Diff current 2 Id In Y 000 Limit value Id IN monitoring step 2 Y2 0 to 300 This value determines the vertical position...

Страница 32: ...exceeds the limit configured in the parameter Release value Overexcit tripping of the differential current 1 is restrained The subsequent screens will be displayed OFF No restraint occurs with over ex...

Страница 33: ...or the unit circuit breaker must be disconnected at the unit circuit breaker The field rotation must be monitored for proper rotation Any absence of or incorrect connection of voltage measuring device...

Страница 34: ...w voltage side 1 B k High voltage side LV Tr HV Tr B V V k VTR LV Transformer rated voltage low voltage side VTR HV Transformer rated voltage high voltage side Example Id ESDR 20 0 2 Iw prim HV 100 A...

Страница 35: ...e already displayed the equipment should be shut down and the transformer assignment checked Testing with Cyclical Swapping With the system off the secondary connections of the CTs should be rotated b...

Страница 36: ...h the rated current If this is not the case e g with tapped trans formers the threshold value of the differential protection may have to be corrected to less sensitive values Determining the maximum d...

Страница 37: ...9 30 31 32 33 65 0 mm 55 8 mm 4 0 mm 46 5 mm 4 6 mm 5 8 mm 24 Section A operation and error messages 25 26 L1 4 0 mm 5 6 mm L2 L3 144 0 mm 180 0 mm 132 0 mm A 8 0 mm 110 0 mm 45 0 mm 16 5 mm A optiona...

Страница 38: ...O Resistive load GP VCont relay output AC 2 00 Aac 250 Vac DC 2 00 Adc 24 Vdc 0 36 Adc 125 Vdc 0 18 Adc 250 Vdc Inductive load PD VCont relay output AC B300 DC1 00 Adc 24 Vdc 0 22 Adc 125 Vdc 0 10 Adc...

Страница 39: ...ge aft 1 to 99 s 1 s Diff current 1 relay outp 0000 1 3 Diff current 2 relay outp 0000 1 3 Range monit Id relay outp 0000 1 3 inrush deteced relay outp 0000 1 3 BASIC SETTINGS Nominal current 10 to 9...

Страница 40: ...t LV circuit arrangement 0 Yz5 HV circuit arrangement LV Z circuit arrangement 5 30 150 Dz0 HV circuit arrangement LV Z circuit arrangement 0 Yd11 HV circuit arrangement LV circuit arrangement 11 30 3...

Страница 41: ...t cases your problem can be resolved over the phone If not you can select which course of action you wish to pursue based on the available services listed in this section Returning Equipment for Repai...

Страница 42: ...ce Department in Stuttgart 49 0 711 789 54 0 They will help expedite the processing of your order through our distributors or local service facility To expedite the repair process contact Woodward in...

Страница 43: ...one of the following international Woodward facilities to obtain the address and phone number of the facility nearest your location where you will be able to get information and service Facility Phone...

Страница 44: ...a our toll free or local phone numbers e mail us or use our website and refer ence technical support Product Training is available on site from several of our worldwide facilities at your location or...

Страница 45: ..._____________________ Control see name plate Unit no and revision P N ___________________ REV ____________ Unit type ESDR 4T __________________________________ Serial number S N ______________________...

Страница 46: ...70565 Stuttgart Germany Phone 49 0 711 789 54 0 Fax 49 0 711 789 54 100 sales stuttgart woodward com Homepage http www woodward com power Woodward has company owned plants subsidiaries and branches as...

Отзывы: