ID
Parameter
CL
Setting range
[Default]
Description
The slope of the ramp is used to
alter the rate at which the
controller modifies the setpoint
value. The faster the change in
the setpoint is to be carried out,
the greater the value entered here
must be.
7494
7495
7496
Unit
2
User-defined up to 6 characters
text
[ _ _ _ _ _ _ ]
This parameter is assigning a unit
text to the displayed analog value.
Notes
This parameter may only be
configured using ToolKit.
The max. number of characters is
39 but depends on numbers of
Bytes for each character. The
Bytes/character are defined by the
font of the currently selected
language.
Up to six characters are
best for display/HMI; more will
override screen border/frame.
Please verify the length on the
display for best view!
4.4.4.7
Discrete Raise/Low Function
General notes
In operation modes MANUAL, TEST and AUTOMATIK the frequency / load and voltage /
reactive power setpoints may be raised and lowered using the LogicsManager
functionality, i.e. it is possible to use LogicsManager command variables to raise and
lower these setpoints. In this case the discrete raise/lower function always starts with the
rated value (frequency / load and voltage / reactive power).
Most commonly a button may be used to energize a discrete input on the control, which is
used again as a LogicsManager command variable to enable the respective
LogicsManager function to change the setpoint.
For related information refer to
╚═▷ “4.1.5.8 Setpoints generator”
Frequency and voltage may be adjusted within the configured operating limits (
“4.5.1.1 Generator Operating Ranges: Voltage / Frequency / Busbar”
). Active power may
be adjusted between 0 and the configured load control setpoint maximum
(parameter
). The power factor may be adjusted between 0.71 leading and 0.71
lagging.
ID
Parameter
CL
Setting range
[Default]
Description
12900
Discrete f/P +
2
Determined by LogicsManager
86.21
[(0 & 1) & 1]
Once the conditions of the
LogicsManager have been fulfilled,
the frequency / load setpoint will
be raised.
378
easYgen-3000XT Series
B37574
4 Configuration
4.4.4.7 Discrete Raise/Low Function