This screen displays the diagnostic status (the current communication state of the load
share and system bus) of the accepted easYgen devices. Refer to
4.1.5.8
Setpoints generator
Fig. 101:
Setpoints screen 1: P and PF/kvar
The setpoint is displayed on the left and the actual value is displayed on the right half of
the screen.
The source, which is used for setpoint 1 or setpoint 2, is displayed with the respective
AnalogManager function number.
The setpoints may only be adjusted if the respective controller is enabled. Frequency and
voltage may be adjusted within the configured operating limits.
Active power may be adjusted between 0 and the configured load control setpoint
maximum. The power factor may be adjusted between 0.71 leading and 0.71 lagging.
The source (e.g. “05.54 Internal P setp1 [kW]” like shown in the screenshots) can only be
displayed if the corresponding AnalogManager (e.g. “AM ActPower SP1 [kW]”) is set to
type “Pass through”. Otherweise the name of the selected AnalogManager e.g. “AM
ActPower SP1 [kW]” will be displayed.
141
easYgen-3000XT Series
B37574
4 Configuration
4.1.5.8 Setpoints generator
Released