ID
Parameter
CL
Setting range
[Default]
Description
5796
Load setpoint 3
2
Import
The value entered for the import
level shall always be supplied by
the utility. All load swings are
absorbed by the generator(s)
provided the load rating for the
generator(s) is not exceeded. The
generator will always start when
an import power operation is
enabled.
Export
The value entered for the export
level shall always be supplied to
the utility. All load swings are
absorbed by the generator(s)
provided the load rating for the
generator(s) is not exceeded. The
generator will always start when
an export power operation is
enabled.
[Steady]
The generator shall always supply
the value entered for the steady
power level. All load swings are
absorbed by the utility. The
generator will always start when a
steady power (base load)
operation is enabled.
5795
Int. load control
setpoint 3
(Internal load control
setpoint 2)
2
0.0 to 99999.9 kW
[150.0 kW]
The load setpoint 3 is defined in
this screen. This value is the
reference for the load controller
when performing parallel
operations.
5606
AM ActPower SP3
[kW]
2
Determined by AnalogManager
81.07
[A1 = 05.80 Internal P setp3
[kW]]
The load setpoint 3 source may be
selected from the available data
sources.
The internal load setpoint 05.80
can be changed manually at the
setpoint screen of the display.
Notes
The load setpoint may be adjusted
between 0 and the configured
load control setpoint maximum
(parameter
12998
Setp. 3 load
(Setpoint 3 load)
2
Determined by LogicsManager
87.67
[(0 & 1) & 1]
If this LogicsManager condition is
TRUE and »Setp. 2 load« is not
TRUE, the frequency setpoint 3
will be enabled., i.e. the setting of
parameter
overrides the
setting of parameter
If this LogicsManager condition is
TRUE, the frequency setpoint 3
will be used instead of frequency
setpoint 2. The ActPower SP3
(result of AM)
will be taken into
account.
Notes
For information on the
LogicsManager and its default
359
easYgen-3000XT Series
B37574
4 Configuration
4.4.4.5.2 Configure: Load Setpoints
Released