3.4.3 MANual START/STOP
Engine control is separated from breaker manage‐
ment. Breaker(s) must be manually opened/closed
(supply should be in normal range).
1.
Press the MAN button
ð
The LED next to the button will illuminate to confirm the
operation
2.
Press the START button to start the genset as described
above. I case of abnormal conditions, such as overheating,
low oil pressure, over speed and abnormal voltage during
generator running occur, the controller can protect genset by
stopping quickly.
Pressing can stop the running generator as described
above.
3.5 Transition Procedures
3.5.1 Disconnect during cranking
There are three conditions under control to abort the starting of the
engine:
n
speed sensor
n
generator frequency
n
engine oil pressure
They can be used separately or in combinations.
We recommend selecting all three at the same time: engine oil
pressure together with speed sensor, and generator frequency.
This allows for an immediate separation of the starter motor from
the engine. Additionally, crank disconnect can be checked exactly.
When set to speed sensor, ensure that the number of flywheel
teeth is the same as setting.
Sensor not used? Make sure not to select a
sensor that is not in use. Otherwise, an error mes‐
sage might occur.
If the speed sensor ( “Firing speed RPM” ) is not
selected, the rotating speed displayed on the con‐
troller is calculated from generator frequency and
the number of poles.
If the generator frequency ( “Firing speed Hz” ) is
not selected, the relative power quantity will neither
be registrated nor displayed (e.g. water pump
application).
MANual Start
MANual Stop
Operation
Transition Procedures > Disconnect during cranking
37889A
easYgen-1400 | Genset Control
23
Содержание easYgen-1400
Страница 1: ...easYgen 1400 Operation Manual Genset Control easYgen 1400 37889A...
Страница 10: ...General Information General Information Safety General hazard warnings 37889A easYgen 1400 Genset Control 10...
Страница 14: ...System Overview ToolKit SC Status Screens 37889A easYgen 1400 Genset Control 14...
Страница 26: ...Operation Trouble Shooting 37889A easYgen 1400 Genset Control 26...
Страница 30: ...Appendix Alarms and Warnings Shutdown Alarms 37889A easYgen 1400 Genset Control 30...
Страница 34: ...37889A easYgen 1400 Genset Control 34...
Страница 35: ......