Icons
Keys
Description
Down/Decrease
1) Screen scroll
2) Settings menu: Down cursor and decrease value
3) Open/close GCB in MAN mode
4) Lamp test (hold button for 5 sec)
Right
Set/Confirm
1) Mute horn
2) Settings menu hold button for 5 sec
3) Settings meu: select digit position
4) Return to home page
Alarm
Status
In MANual mode:
Pressing and (START) simultaneously will
force the generator to crank. Successful start will
not be judged according to crank disconnect condi‐
tions, the operator needs to crank the starter motor
manually; Once the engine has fired, the operator
must relase the button. Only then the start output
will be deactivated, safety on delay will start.
WARNING!
Users can change passwords. Please make note
of the new password after changing it. If you forget
the password, please contact Woodward services
and send all device information on the “ABOUT”
page of the controller for legitimation.
3.2 Warning/Alarm Signaling
The Alarm type is visualized with av
“Alarm” LED located beside
the display.
Alarm Indicator LED
Alarm Type
Slow flashing
Warning
Fast flashing
Shutdown or Trip Alarm
ON (permanently illuminated)
Common Alarm, acknowledged
Operation
Warning/Alarm Signaling
37889A
easYgen-1400 | Genset Control
16
Содержание easYgen-1400
Страница 1: ...easYgen 1400 Operation Manual Genset Control easYgen 1400 37889A...
Страница 10: ...General Information General Information Safety General hazard warnings 37889A easYgen 1400 Genset Control 10...
Страница 14: ...System Overview ToolKit SC Status Screens 37889A easYgen 1400 Genset Control 14...
Страница 26: ...Operation Trouble Shooting 37889A easYgen 1400 Genset Control 26...
Страница 30: ...Appendix Alarms and Warnings Shutdown Alarms 37889A easYgen 1400 Genset Control 30...
Страница 34: ...37889A easYgen 1400 Genset Control 34...
Страница 35: ......