Manual 37441C
DTSC-50 - ATS Controller
© Woodward
Page 19/106
Voltage Measuring: Generator 1Ph 2W
Phase-Neutral Voltage Measuring
L1
N
GCB
29
31
33
35
L3
L2
L1
N
Generator voltage 1Ph 2W
G
L1
N
GCB
29
31
33
35
L3
L2
L1
N
Generator voltage 1Ph 2W
G
Figure 6-6: Voltage measuring - generator 1Ph 2W, phase-neutral
Phase-Phase Voltage Measuring
It is also possible to perform a phase-phase voltage measuring. The units is intended for a phase-neutral measur-
ing as described above, but may also be used for phase-phase voltage measuring. In this case, phase L2 must be
connected to the N terminal of the DTSC-50 and the Generator rated voltage (Parameter 11) must be configured
to the phase-phase voltage.
33
35
L1
N
Generator voltage 1Ph 2W
31
29
L3
L2
L1
L2
GCB
G
Figure 6-7: Voltage measuring - generator 1Ph 2W, phase-phase
Terminal
Description
A
max
29
Generator voltage - phase L3
480 Vac 2.5 mm²
31
Generator voltage - phase L2
480 Vac 2.5 mm²
33
Generator voltage - phase L1
480 Vac 2.5 mm²
35
Generator voltage - phase N
480 Vac 2.5 mm²
Table 6-3: Voltage measuring - terminal assignment - generator voltage
NOTE
If you select to perform a phase-phase voltage measuring, the display is still indicating a phase-neutral
voltage since the voltage is measured between terminal 33 (L1) and 35 (N).
However, if the Generator rated voltage (Parameter 11) is configured correctly, the displayed value is
the correct phase-phase voltage value.