Manual 02007
DSLC Digital Synchronizer and Load Control
Woodward
27
Min. Max. Initial Dimen-
Name
Value Value Value sion
12.
Network Error Log
No Error/
Bad
Event/
NV Length Mismatch/
NV Msg Too Short/
EEPROM Write Fail/
Bad Address Type/
Preemption
Timeout/
Already
Preempted/
Sync NV Update Lost/
Invalid Resp Alloc/
Invalid
Domain/
Read Past EndOfMsg/
Write Past EndOfMsg/
Addr Table Index/
Incomplete
Msg/
Update On Output NV/
No Msg Avail/
Illegal
Send/
Unknown
PDU/
Invalid NV Index/
Divide by Zero/
Invalid Appl Error/
Memory Alloc Fail/
Write Net Buffer/
Appl CS Error/
Cnfg CS Error/
Invalid Xcvr Reg/
Xcvr Reg Timeout/
Write Appl Buffer/
IO
Ready/
Self Test Failed/
Subnet
Router/
Authentication/
Self Inst Semaphore/
Read Write Semaphore/
Appl Signature Bad/
Router
Firmware/
Unknown
13.
Net Interface Errors
0
65535
14. A/D
Errors
0
65535
Menu (Set Point) Descriptions
Menu 1—Synchronizer
1.
Sync Gain
determines how fast the synchronizer responds to an error in
speed or phase. Adjust gain to provide stable control during synchronizing.
Lower value to slow response.
2.
Sync Stability
compensates for delay in the synchronizer control loop.
Prevents low frequency hunting and damping (overshoot or undershoot)
when the synchronizer is enabled or a speed transient occurs during
synchronizing.
3.
Slip Frequency Ref
specifies the positive (fast) slip frequency reference
(generator frequency higher than bus frequency) when slip frequency
synchronizing is desired. Setting the slip frequency reference to 0 selects
phase matching synchronizing.
Содержание DSLC
Страница 1: ...Installation and Operation Manual DSLC Digital Synchronizer and Load Control Manual 02007 Revision D...
Страница 11: ...Manual 02007 DSLC Digital Synchronizer and Load Control Woodward 5 Figure 1 1a DSLC Control wye version shown...
Страница 13: ...Manual 02007 DSLC Digital Synchronizer and Load Control Woodward 7 Figure 1 2 Hand Held Programmer...
Страница 17: ...Manual 02007 DSLC Digital Synchronizer and Load Control Woodward 11 Figure 1 4 Control Options...
Страница 67: ...Manual 02007 DSLC Digital Synchronizer and Load Control Woodward 61 Figure 4 1 Synchronizer Block Diagram...
Страница 85: ...Manual 02007 DSLC Digital Synchronizer and Load Control Woodward 79 Figure 7 1 Process Control Block Diagram...