DSLC Digital Synchronizer and Load Control
Manual 02007
12
Woodward
Chapter 2.
Installation
Introduction
This chapter provides the general information for site selection, installation, and
wiring of the DSLC™ control.
Unpacking
Before unpacking the control, refer to the inside front cover of this manual for
WARNINGS and CAUTIONS. Be careful when unpacking the control. Check for
signs of damage such as bent or dented panels, scratches, loose or broken
parts. If any damage is found, immediately notify the shipper.
Location
When selecting a location for mounting the DSLC control, consider the following:
•
Protect the unit from direct exposure to water or to a condensation-prone
environment.
•
The continuous operating range of the DSLC control is –40 to +70 °C (–40
to +158 °F).
•
Provide adequate ventilation for cooling. Shield the unit from radiant heat
sources.
•
Do not install near high-voltage, high-current devices.
•
Allow adequate space in front of the unit for servicing.
•
Do not install where objects can be dropped on the terminals.
•
Ground the chassis for proper safety and shielding.
•
The control must NOT be mounted on the engine.
Installation
Select a mounting location for the DSLC control (see considerations above).
Locate and drill six (6) holes for mounting hardware (not furnished; see Figure
1-1 for locations). Tap the holes for machine screws or bolts. Install the unit and
secure with the mounting hardware.
Electrical Connections
This section covers typical wiring connections, as shown in Figure 1-3. For other
applications, contact Woodward for assistance.
Connect the terminals as shown in Figure 1-3. When making the connections,
observe the following:
•
Make all connections using insulated terminals. Use 0.5 mm² (20 AWG) or
larger stranded wire.
•
Make sure that all wires shown as shielded on the wiring diagram are
stranded, twisted-pair, shielded wire.
•
Do not place shielded wires in the same cable conduits with high-voltage or
high-current carrying cables.
Содержание DSLC
Страница 1: ...Installation and Operation Manual DSLC Digital Synchronizer and Load Control Manual 02007 Revision D...
Страница 11: ...Manual 02007 DSLC Digital Synchronizer and Load Control Woodward 5 Figure 1 1a DSLC Control wye version shown...
Страница 13: ...Manual 02007 DSLC Digital Synchronizer and Load Control Woodward 7 Figure 1 2 Hand Held Programmer...
Страница 17: ...Manual 02007 DSLC Digital Synchronizer and Load Control Woodward 11 Figure 1 4 Control Options...
Страница 67: ...Manual 02007 DSLC Digital Synchronizer and Load Control Woodward 61 Figure 4 1 Synchronizer Block Diagram...
Страница 85: ...Manual 02007 DSLC Digital Synchronizer and Load Control Woodward 79 Figure 7 1 Process Control Block Diagram...