Woodward 

Control Overview 

 
The 505E Digital Governor is designed to control extraction, extraction/ 
admission, or admission steam turbines. The difference between these turbines 
is the capability of the turbine to allow low pressure steam, which is at a lower 
pressure than the inlet, to enter and/or exit the turbine. An extraction turbine 
allows the lower pressure (extraction) steam to exit the turbine only and will have 
a non-return valve in the extraction header/line to prevent steam from entering 
the turbine. An admission turbine (also called induction) will allow excess header 
steam to enter the turbine through the low pressure inlet. An extraction/admission 
turbine will allow low pressure header steam to enter or exit the turbine 
depending on system pressures. A turbine with admission capability will have a 
stop valve or trip-and-throttle valve in the low pressure line to prevent steam from 
entering the turbine when the unit is tripped. The type of turbine used will depend 
on the system requirements and must be designed by the turbine manufacturer 
to perform the functions required. 
 
The 505E has two independent control channels available, the speed/load and 
auxiliary controllers. The outputs of these two controllers are low-signal-selected 
(LSS) to provide to speed/load demand signal to the ratio/limiter. In addition to 
these channels, the speed/ load controller can be manipulated by another 
controller, the cascade controller. The cascade controller is ‘cascaded’ into the 
speed controller, whereby the speed controller setpoint is changed directly by the 
cascade controller output. The auxiliary controller can act as either a control 
channel or as a limiting channel. All three of these PID controllers have the 
option of utilizing an analog input signal to remotely position their setpoints. 
Additional features of the 505E include frequency control, isochronous 
loadsharing, critical speed avoidance, idle/rated control, and an automatic start 
sequence. There are two serial communications ports which can be used to 
monitor and control the turbine using Modbus protocol. 
 
 

Extraction Turbines 

 
The 505E control can be configured to operate single automatic extraction 
turbines by controlling the interaction of the governor (HP or high pressure) valve 
and the extraction (LP or low pressure) valve. (The 505E can also operate the 
governor valve and the first extraction valve of multiple extraction turbines). 
 
Single automatic extraction turbines have a high pressure stage and a low 
pressure stage, each controlled by a valve. Steam enters the turbine through the 
HP valve (see Figure 1-2). At the downstream end of the HP turbine stage and 
before the LP valve, steam can be extracted. The LP valve controls the entry of 
steam into the LP turbine stage, and the diverting of steam through the extraction 
line. As the LP valve is opened, more steam enters the LP stage and less is 
extracted. 
 
In most cases, the operator of an extraction turbine needs to maintain both 
turbine speed/ load and extraction pressure/flow at constant levels. Changing the 
position of either the HP valve or the LP valve affects both turbine speed/load 
and extraction. If either the load on the turbine or the extraction demand 
changes, both the HP valve position and the LP valve position must be changed 
to maintain speed/load and extraction. The movement of both valves is 
automatically calculated by the 505E’s ratioing logic based on the turbine 
performance parameters to minimize valve/process interaction. 
 

 

Содержание 505E

Страница 1: ...roduct Manual 85018V1 Revision E Original Instructions 505E Digital Governor for Extraction Steam Turbines Volume 1 Manual 85018 consists of 2 volumes 85018V1 85018V2 Installation and Operation Manual...

Страница 2: ...ge including damage to the equipment Any such unauthorized modifications i constitute misuse and or negligence within the meaning of the product warranty thereby excluding warranty coverage for any re...

Страница 3: ...24 Introduction 24 Mechanical Data and Hardware Installation 24 CHAPTER 3 505E CONTROL DESCRIPTION 42 Introduction 42 Ratio Limiter Configurations 42 Speed vs Extr Adm Priority 49 Turbine Start 51 Tu...

Страница 4: ...DYN Key Screens 162 Stop Key Screens 163 Auxiliary AUX Key Screens 164 Remote Speed Bias RMT Key Screens 167 Cascade CAS Key Screens 170 Extraction Admission EXT ADM Key Screens 173 Alarms 176 Trips...

Страница 5: ...l RS 232 Communications 39 Figure 2 11 Typical RS 422 Communications 39 Figure 2 12 Typical RS 485 Communications 40 Figure 2 13a Preferred Multipoint Wiring 41 Figure 2 13b Alternate Multipoint Wirin...

Страница 6: ...17 ALARM Screen 177 Figure 5 18 TRIP Screen 178 Figure 5 19 Typical Response to Load Change 182 Figure 6 1 ASCII RTU Representation of 3 184 Figure 6 2 Modbus Frame Definition 185 Table 1 1 505s with...

Страница 7: ...Read Addresses 191 Table 6 7b Analog Read Addresses 192 Table 6 7c Analog Read Addresses 193 Table 7 8 Analog Write Addresses 193 Table 6 9a Control Status 194 Table 6 9b Control Status 195 Table 6 10...

Страница 8: ...mover control system An overtemperature or overpressure shutdown device may also be needed for safety as appropriate Personal Protective Equipment The products described in this publication may prese...

Страница 9: ...sed by improper handling read and observe the precautions in Woodward manual 82715 Guide for Handling and Protection of Electronic Controls Printed Circuit Boards and Modules Follow these precautions...

Страница 10: ...B C D T3B at 60 C Ambient rear enclosure provided T3C at 65 C Ambient rear enclosure omitted For use in Canada and the United States UL File E156028 Other International Compliance C Tick ACA RSM Decl...

Страница 11: ...er supply or control boards unless the area is known to be non hazardous RISQUE D EXPLOSION Ne pas raccorder ni d brancher tant que l installation est sous tension sauf en cas l ambiance est d cid men...

Страница 12: ...505E Digital Governor Manual 85018V1 x Woodward...

Страница 13: ...al 85017 describes the 505 Digital Governor for steam turbines without extraction pressure control Part Number Options Part Number Power 9907 165 HVAC 180 264 Vac 9907 166 AC DC 88 132 Vac or 90 150 V...

Страница 14: ...sous tension sauf en cas l ambiance est d cid ment non dangereuse La substitution de composants peut rendre ce mat riel inacceptable pour les emplacements de Classe I applications Division 2 ou Zone...

Страница 15: ...g is defaulted to zero but can be adjusted up to 3000msec using the debug mode MAIN AIx LATCH_DLY where x is the analog input number Added a tunable single pole filter LAG to each analog input Output...

Страница 16: ...ficed Modbus is a trademark of Schneider Automation Inc Additional Features The 505E also provides the following features First Out Trip Indication 5 total trip inputs Critical Speed Avoidance 2 speed...

Страница 17: ...and F4 can be used to enable or disable various functions of the control Control Outputs Two actuator outputs with linearization curves for the HP and the LP valve outputs Six 4 20 mA outputs for mete...

Страница 18: ...505E Digital Governor Manual 85018V1 6 Woodward Figure 1 1b Overview of 505E Functionality...

Страница 19: ...Manual 85018V1 505E Digital Governor Woodward 7 Figure 1 1c Overview of 505E Functionality...

Страница 20: ...n act as either a control channel or as a limiting channel All three of these PID controllers have the option of utilizing an analog input signal to remotely position their setpoints Additional featur...

Отзывы: