Woods DASHIO EC TWINBOX Скачать руководство пользователя страница 7

7

7. FAULT-FINDING

Fault-finding must be carried out on the product by appropriately qualified personnel using the correct tools and 
equipment. If in doubt please seek advice from Woods Air Movement.

7.1 Electrical

7.1.1    Isolate the box fan and controls from the electrical supply, check that the electrical connections to the 

product are secure and wired in accordance with the connection diagram,

7.1.2   Check that the voltage applied to the product is as specified on the box fan nameplate.

7.1.3    Connect an ammeter (clamp meter) in line with each phase (one phase in the case of single phase motors) 

of the box fan in turn and check that the current consumption is within the full load current specified on 
the product nameplate.

7.1.4   Ensure that there is no smell of burning in or around the vicinity of the motor.

7.1.5   Check the integral fuses within the iFan controller. Refer to iFan manual.

7.1.6    Three phase units also have additional MCB protection to each motor and a separate MCB that provides a 

single phase supply to the controls circuit. These are found in a separate enclosure inside the unit.

 

Check that these are in a healthy state before undertaking more in depth fault finding.

7.2 Mechanical

  WARNING! 
   

Before any of the following checks are made isolate the fan and controls from the electrical 
supply.

7.2.1    Check that there is no obstruction to the fan impeller, that the blades are clean, and no loose items or 

debris is present in the vicinity of the impeller and inlet/discharge.

7.2.2    Rotate the fan motor shaft by hand. Investigate any sound of internal chaffing, rubbing or resistance.  

Any resistance to smooth rotation may indicate that the bearings require replacement.

7.2.3   Ensure that all fixings are secure.

8. DISPOSAL

When the box fan has completed its working life the metal components should be segregated and recycled. The 
remaining items of material should be safely disposed of in accordance with local health and safety regulations.

Содержание DASHIO EC TWINBOX

Страница 1: ...EC BOX FAN Safety Installation Operation and Maintenance Instructions...

Страница 2: ...IG 5 CONNECTION DIAGRAM EC BOX FAN AND IFAN CONTROLLER 8 10 INSTALLATION EXAMPLES 9 FIG 6 FLOOR MOUNTED ALL SIZES CORRECTLY MOUNTED 9 FIG 7 CEILING MOUNTED SPIGOT SIZES 125 150 200 AND 250MM ONLY CORR...

Страница 3: ...ntacted and supplied with full fan nameplate details before any repair work is undertaken 2 HANDLING STORAGE 2 1 On receipt of the product we recommend that it is checked against what was ordered Befo...

Страница 4: ...ment must be safe for both the fan and for personnel 3 5 Care must be taken to ensure that during extremes of wet and windy weather any ingress of water through the fan will not reach sensitive or haz...

Страница 5: ...e a danger and cause injury If there is any doubt that a safe and reliable installation of the fan can be assured Woods Air Movement or their representative should be contacted for advice See section...

Страница 6: ...e attempted before switching off and completely isolating the product and its controls from all electrical supplies Also allow the rotating parts of the fans to come to rest and the motors to cool 6 2...

Страница 7: ...o iFan manual 7 1 6 Three phase units also have additional MCB protection to each motor and a separate MCB that provides a single phase supply to the controls circuit These are found in a separate enc...

Страница 8: ...I M N I S N O I S N E M I D L L A K U D Z 5 4 O C X E S S E R E T S E H C L O C Y A W L A I X A 5 5 5 2 2 2 6 0 2 1 0 4 4 e n o h p e l e T 7 7 7 2 2 2 6 0 2 1 0 4 4 x a F K S A T B U O D N I F I C L...

Страница 9: ...rectly Mounted IMPORTANT NOTE When mounting on the ceiling in the normal position please ensure suitable drop rods are used Fig 8 Ceiling Mounted Inverted Spigot Sizes 125 150 200 and 250mm only Corre...

Страница 10: ...l Vertical Air Flow Up Sizes 125 150 200 and 250mm Only Correctly Mounted Fig 10 Wall Mounted Vertical Wall Mounted Vertical Air Flow Down All Sizes Incorrectly Mounted Fig 11 Wall Mounted Horizontal...

Страница 11: ...11 NOTES...

Страница 12: ...try application experience The widest range of Air Movement and Ventilation products in the market and strong market presence with over 100 years of experience and manufacturing of products guarantees...

Отзывы: