VENT INSTALLATION 

Figure 8 - Horizontal Vent Termination Location

Vent Terminal

Air Supply Inlet

Area Where Terminals Not Permitted

Inside Corner Detail 

FOR HORIZONTAL TERMINATION

MINIMUM DISTANCES 

A =  Clearance above the grade, a veranda, porch, deck, or balcony [*12" (305mm) minimum]. 
B =  Clearance to window or door that may be opened 

[*12" (305mm) minimum]. 

C =  Clearance to permanently closed window [*minimum 12" (305mm) recommended to prevent condensation on window]  

D

 

=  Vertical clearance to ventilated soffit located above the terminal within a horizontal distance of two (2) feet (610mm) from 

the centerline of the terminal [18" (457mm) minimum].  

E

 

=  Clearance to unventilated soffits [12" (305mm) minimum]. 

Clearance to vinyl soffit [30" (762mm)]. 

F =  Clearance to an outside corner 

[*6" (152mm) minimum].

G = Clearance to an inside corner 

[*6" (152mm) minimum].

H = *Not to be installed above a gas meter/regulator assembly within three (3) feet (914mm) horizontally from the centerline of 

the regulator. 

I =  Clearance to service regulator vent outlet [*3' (914mm) minimum]. 
J =  Clearance  to  non-mechanical  air  supply  inlet  to  building  or  the  combustion  air  inlet  to  any  other  appliance  [*12" 

(305mm)minimum]. 

K =  Clearance to a mechanical air supply inlet [*6' (1829mm) minimum]. 
L

 

=  Clearance above a paved sidewalk or paved driveway located on public property [

**

7' (2133mm) minimum]. 

M

 

= Clearance under veranda, porch, deck, or balcony [*12" (305mm) minimum

***

].

N = Clearance above a roof shall extend a minimum of 24" (610mm) above the highest point when it passes through the roof 

surface and any other obstruction within a horizontal distance of 18" (457mm). 

*

As specified in CAN/CGA B149 Installation Codes. Note: Local codes or regulations may require different clearances.

**  A vent must not terminate directly above a sidewalk or paved driveway, which is located between two single-family dwellings 

and serves both dwellings.

***  Only permitted if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor.

Always maintain minimum clearances around vent systems. The minimum clearances to 
combustibles for horizontal vent pipe are 

3

" at the top and 1" at the sides and bottom of 

the vent system until the pipe penetrates the nearest vertical wall. A 1" minimum clearance 
all around the pipe must be maintained. Do not pack the open air spaces with insulation 
or other materials. This could cause high temperatures and may present a fire hazard.

WARNING

 

15

Содержание SANTA MONICA N-E

Страница 1: ...ion adjustment alteration services or maintenance can cause injury or property damage Refer to this manual For assistance or additional information consult a qualified installer service agency or the gas supplier CLOTHING OR OTHER FLAMMABLE MATERIAL SHOULD NOT BE PLACED ON OR NEAR THE APPLIANCE YOUNG CHILDREN SHOULD BE SUPERVISED WHEN THEY ARE IN THE SAME ROOM AS THE APPLIANCE CHILDREN AND ADULTS ...

Страница 2: ...nation Configuration 19 Below Grade Installation 21 Vertical Through the Roof Installation 22 Installation for Vertical Termination 23 Cathedral Ceiling Installation 24 Fireplace Installation 25 Check Gas Type 25 Installing Gas Piping to Fireplace Burner Checking Gas Pressure 27 Electrical Installation 28 Electrical Wiring 28 Vent Installation 12 Gas Connection 26 V Glass Frame Removal 29 Firebox ...

Страница 3: ...tion leakage can occur CARBON MONOXIDE POISONING Early signs of carbon monoxide poisoning are similar to the flu with headaches diz ziness and or nausea If you have these signs the fireplace may not have been installed properly Get fresh air at once Have the fireplace inspected and serviced by a qualified service person Some people are more affected by carbon monoxide than others These include pre...

Страница 4: ...the absence 15 This appliance when installed must be electrically rating plate etc in this fireplace Use only the gas type indicated on 14 Do not use any solid fuels wood coal paper cardboard 13 Never place anything on top of fireplace other objects 12 Do not use this fireplace to cook food or burn paper or 21 Young children should be carefully supervised when they are in the same room as the appl...

Страница 5: ...r the Natural Fuel Gas Code ANSI Z223 1 of local codes with the National with local codes or in the absence The installation must conform The appliance is not approved forcloset or recessed installations TESTED TO ANSI Z21 88 2014 CSA 2 33 2014 CGA 2 17 M91 R2009 CSA P 4 1 09 STANDARDS Direct Vent type appliances draw all combustion air from outside of the dwelling through the vent pipe CODE APPRO...

Страница 6: ...rround Material Noncombustible Measuring Tape Piping Complying with Local Codes Electric Drill and Bits Tee Joint Pliers Pipe Sealant Approved for use with Propane LPG Square Resistant to Sulfur Compounds Pipe Wrench I n the USA the appliance must be derated 4 for every 1 000 ft above 2 000 ft elevations at the factory Read this homeowner smanual thoroughly and follow all instructions carefully In...

Страница 7: ...1 8 between covering material and fireplace to allow for metal fireplace front to expand and contract during operation any damages due to covering materials used If tiles are to be applied covering the fireplace face a layer of cement board must Do not fill spaces around firebox with insulation or other materials This could cause a fire be used as a substrate 5 PLEASE NOTE Natural stone products m...

Страница 8: ...ace Dimensions 8 9 GAS AND ELECTRICAL ACCESS HOLES BOTH SIDES FIREPLACE DIMENSIONS SANTA MONICA 22 75 10 5 7 25 7 TOP VIEW 22 75 _ _ 16 22 33 25 ELBOW o 43 30 VENT 43 14 75 29 13 75 36 5 35 FRONT VIEW RIGHT SIDE VIEW WITH 30 DEGREE STARTING ELBOW ...

Страница 9: ...bstruct the front opening of the fireplace Do not install in the vicinity where gasoline or other flammable liquids may be stored Vent pipe routing See Venting section found in this manual for allowable venting configurations These units can be installed in a bedroom or bathroom See National Fuel Gas Code ANSI Z233 1 NFPA 54 current edition the Uniform Mechanical Code current edition and Local Bui...

Страница 10: ...de brackets are adjustable from 1 2 to 5 8 to accommodate different thickness of material SECURING FIREPLACE TO FLOOR OR FRAMING Figure 5 Securing Fireplace to Floor and Framing Studs Framing Screws Side adjustable bracket Screws Screws Side adjustable bracket Side adjustable bracket Side adjustable bracket _ _ _ _ _ _ _ _ ____ ____ _ _ _ _ ____ NOTE If installed in mobile home fireplace must be b...

Страница 11: ... the appliance shall be installed on a metal wood or noncombustible material panel extending full width and depth of the appliance WARNING The fireplace face may be completely covered with any non combustible ma terial Allow clearance for removal of front air panel 6 6 6 6 6 6 6 14 minimum 6 90 minimum Minimum 7 from both side walls 12 maximum depth COMBUSTIBLE MANTEL and glass door Make sure that...

Страница 12: ...ion other than permitted by these instructions FINISHING MATERIAL NOTE Any remote wiring i e remote control wall switch and optional fan must be done prior to final finishing to avoid costly reconstruction INSTALLATION INFORMATION VENT INSTALLATION Never obstruct or modify the air inlet or outlet This may create a fire hazard WARNING Read all instructions completely and thoroughly before attemptin...

Страница 13: ...use common vent systems WARNING A Minimum of 4 Clearance to the Top Is Required Along Horizontal Length of Pipe until Flue Pipe Goes Through Nearest Wall WARNING Horizontal sections of this vent system require a minimum clearance of 4 from the top of the pipe and 1 minimum to the sides and bottom Vertical sections of this system require a minimum of 1 clearance to combustible materials on all side...

Страница 14: ...loor level If an offset is needed in the attic additional pipe and elbows will be required You may use a chase with a vent termination with exposed pipe on the exterior of the house See Installing Vent System in a Chase below If pipe is enclosed in chase it is not exposed It is very important that the venting system maintain its balance between the combustion air intake and the flue gas exhaust Ce...

Страница 15: ... air inlet to any other appliance 12 305mm minimum K Clearance to a mechanical air supply inlet 6 1829mm minimum L Clearance above a paved sidewalk or paved driveway located on public property 7 2133mm minimum M Clearance under veranda porch deck or balcony 12 305mm minimum N Clearance above a roof shall extend a minimum of 24 610mm above the highest point when it passes through the roof surface a...

Страница 16: ...e to the bottom of the graph 3 Select the indicated dimension and position the fireplace in accordance with same Example If the vertical dimension from the floor of the fireplace is 11 3 4m the horizontal run to the face of the Example If the vertical dimension from the floor of the unit is 7 2 14m the horizontal run to the face of the outer Sidewall Vent Graph showing the relationship between ver...

Страница 17: ...ed See Figure 13 1 6 6 Maximum H x 9 W wall and frame as shown See Figure 12 229 229 for noncombustible material such as masonry block or concrete a 7 229mm X 229mm rectangle hole H x 9 3 Attach vent pipe assembly to the fireplace Set fire place in front of its permanent location to insure minimum clearances Mark the wall for a 9 vent pipe end Be sure to allow for 1 2 190mm diameter hole is accept...

Страница 18: ... 15 5 Slide the wall thimble over the vent pipe before connecting the horizontal run to the vent cap See Figure 16 6 Carefully move the fireplace with vent assembly attached toward the wall and insert the vent pipe into the horizontal termination The pipe overlap should be a minimum of 11 4 Apply silicone to the outer pipe connection Fasten all vent connections with screws provided 7 Slide the wal...

Страница 19: ... up with the sid ing It is best to locate the fireplace in such a way that minimizes the number of offsets and horizontal vent length The horizontal vent run refers to the total length of vent pipe from the flue collar of the fireplace or the top of the Transition Elbow to the face of the outer wall The Commonwealth of Massachusetts requires the installation and USE of Carbon Monoxide detectors in...

Страница 20: ...tal run the length of the horizontal run MUST be reduced by 18 45cm This does not apply if the 45 elbows are installed on the vertical part of the vent system The maximum number of elbow degrees in a system is 270 See Figure 22 Figure 21 Maximum Vent Run with Elbows Figure 20 Horizontal Run Reduction Figure 22 Maximum Elbow Usage 90 90 Elbow 3 1 2 3 1 2 3 4 7 6 10 B HORIZONTAL TERMINATION CONFIGUR...

Страница 21: ...aving a clearance of approximately 4 below snorkel See Figure 21 3 Install vent system 4 Ensure a watertight seal is made around the vent pipe coming through the wall 5 Apply high temperature sealant caulking supplied around the 4 and 7 snorkel collars 6 Slide the snorkel into the vent pipes and secure to the wall 7 Level the soil so as to maintain a 4 clearance below snorkel See Figure 23 Figure ...

Страница 22: ... in the system is 270 See Figure 26 The minimum height of the vent above the high est point of penetration through the roof is 2 610mm 40 Maximum Height 8 Minimum Height 40 Maximum Height 8 Minimum Height 10 Maximum 10 Maximum 1 2 3 4 1 2 3 4 Support Straps Every 3 Support Straps Every 3 Elbow 2 45 Total Angular Variation 270 Support Straps Every 5 Vertical Restrictor Disk Restrictor Disk Restrict...

Страница 23: ...onnections are fully twist locked See Figure 13 page 17 Figure 27 Offset with Wall Strap and 45 Elbows Roof Flashing Wall Strap 45 Elbows Ceiling Firstop Figure 28 If area above is a room install firestop above framed hole as shown Figure 29 If area above is not a room install firestop below framed hole as shown Continued on next page Firestop Nails Nails Firestop FLAT CEILING INSTALLATION 1 Cut a...

Страница 24: ...Ceiling Support Box Installation Figure 31 Installed Cathedral Ceiling Support Box CATHEDRAL CEILING INSTALLATION IMPORTANT Review all information on previous page before planning this installation Cathedral ceiling installations can be very tricky 1 Remove shingles or other roof covering as necessary to cut the rectangular hole for the support box Mark the outline of the cathedral ceiling support...

Страница 25: ...regulator will reduce incoming gas pressure You must reduce incoming gas pressure to between 11 and 13 inches of water If you do not reduce incoming gas pressure burner system regulator damage could occur Install external regulator with the vent pointing down as shown in Figure 32 Pointing the vent down protects it from freezing rain or sleet External Regulator 100 lb min Propane LP Supply Tank Ve...

Страница 26: ...ps moisture and contaminants This keeps them from going into the burner system gas controls If sediment trap drip leg is not installed or is installed wrong burner system may not run properly Figure 33 Gas Connection Tee Joint Pipe Nipple Cap Approved Flexible Gas Line CSA Design Certified Equipment Shutoff Valve with 1 8 NPT Tap Sediment Trap Drip Leg Natural Gas From Gas Meter 5 W C to 10 5 W C ...

Страница 27: ...ontrol Control Shaft Control Knob Switch Bracket Blower Plug In Duplex Outlet Located underneath firebox floor against Blower Location Side View Strips Exhaust Port Screw Green Ground Wire Spade Terminals Lower Firebox Cavity FRONT BACK see page 5 BLOWER FAN LOCATION Outlet Pressure Tap Pilot Adjustment Inlet Pressure Tap lower right outside wall as shown on page 5 Velcro 2 The appliance and its a...

Страница 28: ...on and Canadian Electrical Code CSA C22 1 WARNING Label all wires before disconnecting when servicing controls Wiring errors can cause improper and dangerous operation CAUTION This fireplace requires 110V AC electrical supply for normal operation in order to power up blower and 7V DC adapter which is required to operate Remote Control However during power outage situation its electronic system DFC...

Страница 29: ...OTE Avoid contacting the glass to any 29 SAFETY SCREEN AND GLASS DOOR REMOVAL Continued on the Next Page Front air panel Left side panel Right side panel Glass door with weld on top bracket and Washers Nuts Springs spring washer nut stud surface and be careful to not damage ...

Страница 30: ...ding the Safety Screen in upper position if necessary by lifting up and moving out to the center STEP 2 Remove the left and right side panels STEP 3 Lift and remove the Safety Screen STEP 4 Locate 3 three 1 4 nuts holding springs on top of the glass frame Using a 7 16 ratchet remove all three nuts and then springs and washers from the studs SAFETY SCREEN AND GLASS DOOR REMOVAL 30 ...

Страница 31: ...HE STUD IS EXPOSED SAFETY SCREEN AND GLASS DOOR REMOVAL 31 WARNING If there is broken glass wear protective gloves to carefully remove from the appliance DO NOT OPERATE THE APPLIANCE ofthelowerchannel andremovebyanglingthe framedownto the left STEP5 Carefullylifttheglassdoorassemblyout ...

Страница 32: ...acket and Glass Frame out from the fireplace 2 Fill the tray with glass media supplied Do not place media on burner or block air flow between burner and tray as shown 3 Place Log 1 behind the burner as shown 4 Place Log 2 next to Log 1 as shown Do NOT place the log directly on the pilot assembly 5 Place Log 3 in front of the burner as shown Continue on next page 32 ...

Страница 33: ... next to Log 3 as shown Safety screen both side panels and Front Air panel If any scratches occur on painted surfaces they can be touched up 9 Place Log 6 next to Log 5 as shown 10 Double check that neither pilot nor burner ports are blocked with the logs or glass media Replace the Glass frame with light coat of high temperature spray paint STOVE BRIGHT 1990 Satin Black can be ordered from Woodbri...

Страница 34: ...or this appliance Any safety screen guard or barrier removed for servicing the appliance must be replaced prior to operating the appliance STEP 1 Remove front air panel and both side panels STEP 2 Angle the safety screen as shown on the picture and carefully bring into the fireplace opening STEP 3 Position the safety screen inside of the fireplace in front of the glass door Locate the two small ve...

Страница 35: ...tabs in the panel with the slots in the face and slide downward Make sure the side panel is secured properly Repeat Steps 5 and 6 for the Left Side Panel STEP 7 Angle the Air Front Panel beneath the bottom of the screen Support the Air panel on the left and right Side Panels STEP 8 Tilt the Panel down to rest on the face support 35 ...

Страница 36: ...ss panel close access panel Open access panel See counterclockwise 10 Turn on all electric power to the appliance See REMOTE Close access panel the Remote Control OPERATING INSTRUCTIONS 36 in Owner s Manual ...

Страница 37: ...d insert into the battery bay as indicated on the battery covel 2 Place the 3 posilion slider switch in the REMOTE position 3 Insert the end of a paper clip into the hole marked PRG on the receiver front cover The receiver will beep three times to indicate that it is ready to syn chronize with a transmitter 4 Install the 3AAA batteries in the transmitter battery bay located on the base of the tran...

Страница 38: ...he set temperature is now displayed see Figure 32 2 Adjust the set temperature by pressing the up or down arrow keys until the desired set temperature is displayed on the LCD screen see Figure 32 Room Temperature Set Temperature Figure 30 Remote Control Display in Farenheit and Celsius board will open the main valve outlet and the main burner will ignite A single beep from the receiver will confir...

Страница 39: ...o beep will sound from the receiver when a transmitter command is sent Replace batteries when this happens Transmitter The life span of the transmitter batteries depends upon various factors battery quality number of appliance ig nitions number of thermostat set point changes etc When the transmitter batteries arc low an icon will appeal on the LCD display see Figure 4a Replace batteries when this...

Страница 40: ... be ordered from the manufacturer Do not use substitute materials Clean the ceramic glass periodically Condensation will some times form on the glass during a cold startup This is normal for all gas fireplaces and inserts This condensation often attracts dust and lint to the surface of the glass The initial paint curing of the appliance can also leave a slight film on the glass This is a temporary...

Страница 41: ...used Replace any glass that is chipped cracked or broken Replacement glass door assemblies MUST be supplied by the fireplace Never operate the fireplace if the glass is broken Never operate the fireplace without the glass door properly secured Keep children and pets a safe distance away NEVER use abrasive materials Do not remove the glass when hot Allow glass to cool before removal When cleaning t...

Страница 42: ...ion Cap 46DVA HC 2 1 High Wind Vertical Termination 46DVA VCH 3 6 6 Pipe Length 46DVA 06 3 6 9 Pipe Length 46DVA 09 3 6 12 Pipe Length 46DVA 12 3 6 24 Pipe Length 46DVA 24 3 6 36 Pipe Length 46DVA 36 3 6 48 Pipe Length 46DVA 48 4 6 11 To 14 5 8 Pipe Adjustable 0911 4 6 17 To 24 Pipe Adjustable 0917 5 6 45 Elbow 46DVA 45 6 6 90 Elbow 46DVA 90 7 6 Flashing 0 12 To 6 12 Roof Pitch 46DVA F6 8 6 Storm ...

Страница 43: ...ILLUSTRATED PARTS LISTS continued CONTROL COMPARTMENT BURNER COMPARTMENT FIREBOX COMPONENTS 2 3 4 5 6 14 1 7 13 8 10 11 12 15 15 16 17 18 19 21 23 24 25 9 FIREPLACE COMPONENTS 18 22 20 21 26 43 ...

Страница 44: ...CPI IPI MODE 120 Vac INPUT 7 Vdc STABILIZED SUPPLY OUTPUT MOTOR IPI CPI RECEIVER DC SUPPLY SPLIT FLOW ON OFF TPTH TH DFC SUPPLY DC SUPPLY GROUND 885 PROFLAME Orange Green Chassis connection Remote control GTM This diagram shows replaceable SIT Proflame parts used in your fireplace 11 25 24 23 1 5 6 26 44 ...

Страница 45: ...OL DFC BOARD 1 7 A100010 A100010 THERMOSTAT BLOWER WITH SPEED CONTROL 1 8 D200020 D200020 VALVE BRACKET 1 10 W100071 W100071 BURNER 1 11 C200003 C200004 PILOT ASSEMBLY 1 12 D100019 D100019 PILOT BRACKET 1 13 F200100 F200100 3 8 NPT X 5 16 COMPRESSION CONNECTOR 1 9 D300015 D300016 ORIFICE 1 14 F200064 F200064 3 8 NPT X 3 8 FLARE CONNECTION 1 15 I100015 I100015 FIREBOX GASKET 1 16 D100059 D100059 ME...

Страница 46: ...n chamber Ensure that the glass is properly secure and latch Frequent pilot outage A Pilot flame may be too high or A Clean and adjust the pilot flame for maximum flame impingement The pilot and main A Inner vent pipe leaking exhaust A Check for flue product leak Replace defective pipe section Flame burn blue and A Insufficient oxygen being supplied A Ensure that the vent cap is installed properly...

Страница 47: ...0 Elbows Quantity 45 Elbows ALTITUDE Feet Above Sea Level Was Stove Derated Yes No If Yes To What Orifice Size Unusual Structure Near Vent Inside Corner Trees Shrubs Other Termination Please Describe Prevalent Wind Conditions Other Installation Notes The installer should complete the form below that describes the details of the installation Having this written record of installation information av...

Страница 48: ... neglect misuse abuse alterations negligence of others including the installation thereof by unqualified installers 2 the costs of removal reinstallation or transportation of defective parts on the appliance or 3 incidental or consequential damage All service work must be performed by an authorized service representative This warranty is expressly in lieu of other warranties express or implied inc...

Отзывы: