10

                MKS

               MUS

Type

85

100

140

190

250

340

420

500

85

100

Output range

kW

70-100

85-120

110-160

160-230

200-300

280-380

360-460

420-550

70-85

85-100

Min. boiler output
burner stage 1

kW

51

60

84

114

150

204

252

300

51

60

Fill water / burner connection

Fill water

Water guidelines for heating systems in accordance with VDI 2035 at operating
temperatures up to 100 °C:

Burner connection

Observe the TRD 411 (oil combustion) and TRD 412 (gas combustion) guidelines.
The gas installation and operation of heating systems must comply with the DVGW
Code of Practice "Gas" and the technical connection conditions of your gas supply
company and/all local regulations.

Burner size

MKS-85-140

Acc. to EN 226 adjustable to burner size

connection

MKS-190 -

Burner plate in acc. with blast tube dia.

MKS-500

cut-out and tap thread.

Match the door insulation to the blast tube diameter of the burner.

The blast tube must protrude into the combustion chamber at least 25 mm beyond the
door installation.

Use fixing screws for the burner flange, which cannot the inserted into the boiler
door more than 15 mm.

Connect the ventilation fitting at the sight glass with the burner fitting.

After the control unit installation, plug the burner cable into the burner.

Ensure that the combustion output matches the rated boiler output.

Observe the details provided by the burner supplier.

To prevent the system falling below the dewpoint, the following minimum boiler output
for two-stage burners are required for the first stage:

Minimum boiler output

*)

for exceptions see VDI 2035

(+) may be required, see VDI 2035

Water guidelines for heating systems in accordance with VdTÜV guidelines at
operating temperatures above 100 °C:

Filling and

top-up water

Circulating water

Residual hardness

mval/kg

pH value

Diamide

Na

2

SO

3

p value

mval/kg

<0.03

0.5-1.5

8.5-10.0

0.5-25

10-40

Group

Total of rated

boiler output Q

Filling and top-up

water

Heating water

Total alkaline

earths in mol/m³

pH value

 

 Diamide

Na

2

SO

3

Excess in mg/kg

0

 ≤

100

-*)

-

-

-

1

100 < Q 

 ≤

350

1 to 3

8 to 9.5

-

-

2

350 < Q 

 ≤

1000

1 to 2

8 to 9.5

2 to 5(+)

5 to 20(+)

kW

Excess in mg/kg

Содержание MKS 140

Страница 1: ...n instructions for the Unit pressure jet oil burner is included in the pressure jet oil burner pack The control unit installation and service instructions included in the control unit pack Wolf GmbH 84048 Mainburg Postfach 1380 Telephone 49 8751 74 0 Fax 49 8751 741600 Partno 3048034 03 03 TV GB ...

Страница 2: ...ion in accordance with EN 303 and EC Directive 90 396 EEC gas consuming equipment 73 23 EEC Low Voltage Directive 89 336 EEC EMCDirective 92 42 EEC HotWaterBoilerEfficiency and93 68 EEC Identification Directive for heating systems with heating circuit pumps and flow temperatures up to 110 C and 4 bar permissible operating pressure in accordance with DIN 4751 and max DHW cylinder pressure 10 bar in...

Страница 3: ...25 125 125 Foundation plinth Height mm 80 80 80 80 80 80 80 80 80 80 80 80 80 Width mm 800 850 800 850 800 850 1000 950 1000 950 1100 1100 1100 Length mm 1360 1300 1360 1300 1700 1500 1850 1500 1850 1500 2000 2000 2000 Boiler flow flange DN 65 65 65 80 80 100 100 100 Safety flow air vent valve male thread R 1 1 1 1 1 2 2 2 Boiler return flange DN 65 65 65 80 80 100 100 100 Filling draining safety ...

Страница 4: ...ts output range which is stated in the specification supplied by WOLF Appropriate use of the boiler refers to the exclusive use in hot water heating systems in accordance with DIN 4751 Never remove bypass or otherwise disable any safety and monitoring equipment Only operate the boiler in perfect technical condition Any faults and damage with a potential impact on safety which might limit the safe ...

Страница 5: ...ystem has been shut down Position the boiler horizontally or slightly rising towards the back to ensure adequate venting of any trapped air Boilers should not be installed in areas subject to aggressive vapours or very dusty highly humid conditions workshops washrooms hobby rooms etc The combustion air must be free from halogenated hydrocarbons e g as contained in sprays solvents and cleaning flui...

Страница 6: ...front and secure with adhesive strips 8 Sidepanels Push the l h r h casing over the rear panel and secure with the screws MUS 85 to 100 MKS 85 to 140 M8x16 supplied to the lower two spacers 8 Sidepanels Secure the l h r h front and rear panels with screws M6x10 then push over the rear panel MKS 190 to 500 and secure with the screws M8x16 supplied on the lower three spacers 9 Wolflabel Hook into th...

Страница 7: ...t out Adjust the setscrew in accordance with the scale Install in reverse order Changing the setting of the high limit safety cut out STB for R31 STAV Observe the respective installation and operating instructions for R32 R33 and R33 4 control units Burnercable 1st stage 2nd stage Boilersensor Mainssupplycable Heatingcircuitpumpcable Loadingpumpcable DHWcylindercable Adjusting the boiler thermosta...

Страница 8: ...n using pipes which are not impermeable to oxygen The boiler and central heating system may only be filled if a type tested safety valve opening pressure max 3 bar has been installed at the ventilation connection of the boiler Install a filling drain valve to fill the central heating system at the drain filling connection and connect a water hose Observe the pressure gauge in the safety equipment ...

Страница 9: ...QN Rated boiler output in kW cp Specific energy 4 2 kWs kgK ρW Specific weight of water 1000 kg m t Temperature differential between the flow temperature and bypass temperature recommended design temperature differential 30k The shunt pump head results from the boiler pressure loss at the selected volume flow the pipework pressure loss as well as all individual boiler circuit pressure losses A ret...

Страница 10: ...ast 25 mm beyond the door installation Use fixing screws for the burner flange which cannot the inserted into the boiler door more than 15 mm Connect the ventilation fitting at the sight glass with the burner fitting After the control unit installation plug the burner cable into the burner Ensure that the combustion output matches the rated boiler output Observe the details provided by the burner ...

Страница 11: ...als for safety pressure switch Control unit junction box Terminals for remote pressure monitoring Burner connection To the control unit To the control unit ye gn P E bl N br L1 P E L1 N br L1 bl N ye gn PE blk ye gn blu br w gr r 2 3 4 1 blk ye gn bl br w gr r To the control unit Remove the burner plug from the control unit connect the black to the brown core and connect the white core to the burn...

Страница 12: ...est permissible water level on the water level indicator The pipework between the boiler the expansion vessel and the safety valve must not be able to be shut off A valve which has been protected against unauthorised closure e g a cap valve would also be acceptable Thesystemdiagramonlyindicatesthesafetyrequirementsbutisnotarecommendation for specific types of heating network control Fresh air vent...

Страница 13: ...ns of supply lines and blow off lines Safetyvalve Diaphragm safety valve Blow off output in kW 50 100 200 350 600 Size internal diameter DN 15 20 25 32 40 Fitting thread for supply line G G G 1 G 1 G 1 Fitting thread for blow off line G G 1 G 1 G 1 G 2 The water and gas chamber of pressure expansion valves must be calculated in accordance with DIN 4807 part 2 If the permissible operating pressure ...

Страница 14: ...is protected above 3 bar or which has a rated output higher than 350 kW with a maximum pressure switch type tested according to VdTÜV Code of Practice Issue 100 l Monitor the operating pressure of hot water heat generator systems with a minimum pressure switch type tested in accordance with the VdTÜV Code of Practice Issue 100 I in order to prevent water evaporating inside the heating system as a ...

Страница 15: ...cross sections Rated output in kW Required chimney size in cm x cm Effective chimney height in m Effective chimney height in m Rated output in kW Please note We recommend that you let your chimney manufacturer design the chimney Square cross sections Required chimney diameter in cm ...

Страница 16: ...lue gas collector box to approx 3rd quarter of 98 16 08 017 X X X Sight glass flat packing 39 01 040 X X X X X X X X Cleaning brush 24 40 240 X X Cleaning brush 24 40 241 X Cleaning brush 24 40 242 X X Cleaning brush 24 40 243 X X X Sight glass 24 00 125 X X X X X X X X Sensor well up to model M 2850 45 00 150 X X X X X X X X Sensor well from model M 2851 24 25 070 X X X X X X X X Turbulators 89 0...

Страница 17: ...ed OFF Oil filter clogged Replace oil filter Heating circuit System in summer mode Check summer winter switch position pump does not start Heating circuit pump locked up Turn the pump shaft with a screwdriver Heating circuit pump faulty Replace the heating circuit pump Cylinder loading pump DHW cylinder thermostat faulty Check the DHW cyl thermostat and replace if nec does not run DHW loading pump...

Страница 18: ...18 Notes ...

Страница 19: ...19 Notes ...

Страница 20: ...nich ID of the named body CE0036 Applied standards TRD702 and specifications DINEN297and656 We WolfGmbH Industriestraße1 84048Mainburg herebydeclarethattheaboveboilercomplieswiththeappropriateregulations laid down in the 97 23 EC Directive when the safety temperature has been set to 110 C This declaration loses its validity if the product is modified without our express permission Observe the safe...

Отзывы: