93
Underfloor heating system
For heating systems with plastic pipes, we recommend the
use of impermeable pipes to prevent the diffusion of oxygen
through the pipe walls.
When operating the condensing boiler in
conjunction with an underfloor heating system,
we recommend sizing the usable volume of a
diaphragm expansion vessel 20 % larger than
recommended by DIN 4807-2. An diaphragm
expansion vessel of insufficient size results in
oxygen ingress into the heating system, causing
corrosion damage.
Please note
If pipes which are impermeable to oxygen are used, an
underfloor heating system can be connected directly to a
heat source with up to 10 kW heating output, depending on
the system pressure drop.
Always install a temperature limiter for the underfloor heating
system to protect the pipes from overheating.
The output of the integrated pump should be increased if
underfloor heating is connected (parameters HG16 and
HG17). Recommendation HG16
Þ
75% and HG17
Þ
100%
For connection of an underfloor heating system with an
output requirement in excess of approx. 10 kW, a 3-way mixer
(accessories MM) and an additional pump are required.
Install a regulating valve in the return; this can be used to
reduce the excessive head of the additional pump if required.
Ensure the system user cannot adjust any
regulating valves.
When using pipes that are diffusion-proof to
oxygen, it is necessary to provide system
separation by means of a heat exchanger.
Inhibitors may not be used.
If an additional heating circuit is operated in parallel to the
underfloor heating system, it must be hydraulically matched
to the underfloor heating system.
Please note
Fig: Underfloor heating system (example
32. Design information, underfloor
heating / DHW circulation
NTC
Sensor resistances
Flow temperature sensor, cylinder temperature sensor, DHW outlet temperature
sensor, outside temperature sensor, return temperature sensor, flue gas temperature
sensor
Temp. °C
Resist. Ω
Temp. °C
Resist. Ω
Temp. °C
Resist. Ω
Temp. °C
Resist. Ω
-17
40810
17
7162
51
1733
85
535
-16
38560
18
6841
52
1669
86
519
-15
36447
19
6536
53
1608
87
503
-14
34463
20
6247
54
1549
88
487
-13
32599
21
5972
55
1493
89
472
-12
30846
22
5710
56
1438
90
458
-11
29198
23
5461
57
1387
91
444
-10
27648
24
5225
58
1337
92
431
-9
26189
25
5000
59
1289
93
418
-8
24816
26
4786
60
1244
94
406
-7
23523
27
4582
61
1200
95
393
-6
22305
28
4388
62
1158
96
382
-5
21157
29
4204
63
1117
97
371
-4
20075
30
4028
64
1078
98
360
-3
19054
31
3860
65
1041
99
349
-2
18091
32
3701
66
1005
100
339
-1
17183
33
3549
67
971
101
330
0
16325
34
3403
68
938
102
320
1
15515
35
3265
69
906
103
311
2
14750
36
3133
70
876
104
302
3
14027
37
3007
71
846
105
294
4
13344
38
2887
72
818
106
285
5
12697
39
2772
73
791
107
277
6
12086
40
2662
74
765
108
270
7
11508
41
2558
75
740
109
262
8
10961
42
2458
76
716
110
255
9
10442
43
2362
77
693
111
248
10
9952
44
2271
78
670
112
241
11
9487
45
2183
79
649
113
235
12
9046
46
2100
80
628
114
228
13
8629
47
2020
81
608
115
222
14
8233
48
1944
82
589
116
216
15
7857
49
1870
83
570
117
211
16
7501
50
1800
84
552
118
205