Heat Recovery unit CWL-300(B) / CWL-400(B) with option PCB
13
Faults
Chapter 5
Fault code
Cause
Action user
Action installer
F2
The input fan has stopped.
Contact the installer.
•
Replace the input fan.
F5
The output fan has stopped.
Contact the installer.
•
Replace the output fan
.
F9
The temperature sensor that
measures the temperature of
WKHLQSXWDLULVGHIHFWLYH
The appliance operates as ex-
pected, but the bypass is out of
operation.
Contact the installer.
•
Check the wiring from the sensor to the
basic pcb.
•
Check the sensor connection to the
wiring.
•
Replace the sensor.
F10
The temperature sensor that
measures the temperature of
WKHRXWSXWDLULVGHIHFWLYH
The appliance operates as ex-
pected, but the bypass is out of
operation.
Contact the installer.
•
Check the wiring from the sensor
to the basic pcb.
•
Check the sensor connection to
the wiring.
•
Replace the sensor.
F11
The postheater sensor is not
FRQQHFWHGGHIHFWLYHVKRUWFLU
-
cuited or it has come loose.
CWL operates as expected, but
the postheater is out of opera-
tion.
Contact the installer.
•
Check the wiring and the connection to
the postheater sensor.
•
Replace the sensor.
5.1 Fault codes table CWL 300/400(B) with option pcb