Flow rate calculation
V
=
k
√
D
p
w
V
in [m³/h] and
D
p
w
in [Pa]
The flow rate is calculated using the effective pressure method. This involves
comparing the static pressure upstream of the inlet nozzle with the static
pressure in the inlet nozzle.
The flow rate can be calculated from the effective pressure Δp
w
(differential pressure of the two static pressures) using the following equation.
The doors must be closed to determine the correct flow rate. Guide the test
hoses over the test connectors towards the outside.
CRL-1300 effective pressure
Δp
[Pa]
43
62
85
111
140
173
209
249
293
V [m³/h] 500
600
700
800
900 1000 1100 1200 1300
The fans used for the CRL-1300 have a k value of 76.
Ef
fective pressure
Δp [Pa]
Flow rate [m³/h]
Δp = effective pressure
(symbolic representation)
20
.
0
70
.
0
120
.
0
170
.
0
220
.
0
270
.
0
320
.
0
450
550
650
750
850
950
1050
1150
1250
1350
V
= 76 x √
D
p
w
CRL-2500 effective pressure
The fans used for the CRL-2500 have a k value of 77.
Ef
fective pressure
Δp [Pa]
Flow rate [m³/h]
Δp = effective pressure
(symbolic representation)
110
.
0
210
.
0
310
.
0
410
.
0
510
.
0
610
.
0
710
.
0
810
.
0
910
.
0
1010
.
0
1110
.
0
850
1050
1250
1450
1650
1850
2050
2250
2450
2650
Δp
[Pa] 137
204
285
379
487
609
744
892 1054
V [m³/h] 900
1100 1300 1500 1700 1900 2100 2300 2500
V
= 77 x √
D
p
w
17 Commissioning
Содержание CRL evo max Series
Страница 25: ...25 3064361_201811 1 2 3 4 12 Unit splitting for handling purposes CRL ...
Страница 26: ...26 3064361_201811 1 2 3 4 12 Unit splitting for handling purposes CRL ...
Страница 27: ...27 3064361_201811 1 2 3 4 12 Unit splitting for handling purposes CRL ...
Страница 28: ...28 3064361_201811 1 2 3 4 12 Unit splitting for handling purposes CRL ...
Страница 29: ...29 3064361_201811 13 Assembly CRL evo max 4x A1 ...
Страница 30: ...30 3064361_201811 13 Assembly CRL evo max 4x 4x B1 B1 A1 ...
Страница 31: ...31 3064361_201811 13 Assembly CRL evo max ...
Страница 51: ...51 3064361_201811 21 Notes ...
Страница 52: ...WOLF GmbH Postfach 1380 D 84048 Mainburg Tel 49 0 87 51 74 0 Fax 49 0 87 51 74 16 00 www WOLF eu ...