34
3064361_201811
15 Siting
Installation location CRL
Indoor unit
The installation location must be level and have adequate load bearing
capacity (see data sheets for individual unit weights). Level the unit
horizontally (align using the adjustable feet). The installation site must be
able to bear the load of the ventilation unit without vibrations on a long term
basis. Provide sufficient space at the front of the unit for maintenance work.
Site the unit in a room that is free from the risk of frost!
Duct connections (ons-
ite)
The unit connectors are rectangular.
Round ducts can be connected directly to the connectors using an adaptor
insulating collar (from square to round).
Insulate the ducts in accordance with applicable regulations and industry
standards.
Adaptor insulating collar for round duct connection on internal unit with vertical
and horizontal duct connection (accessory)
Outdoor air:
AUL / ODA
6801059
48/10
AUL/
ODA
Exhaust air:
FOL / EHA
6801062
48/10
FOL
/EHA
Extract air:
ABL / ETA
ABL/
ET
A
6801061
48/10
Supply air:
ZUL / SUP
6801060
48/10
ZUL
/SUP
Air duct connections are identified
with the following labels:
Hydraulic connection
Heating coil: Hydraulic
connection
example
Cooling coil: Hydraulic
connection
example
Admixing circuit
Benefits: good control
characteristics, low risk of
freezing
Diverting circuit
Benefits: constant flow
temperature in cooling coil,
good dehumidification even at
partial load
Note:
Positioning valves close to the heat exchanger improves the control characteristics
ϑ
1 =
ϑ
2
CRL
1300
2500
3500
4800
6200
9000 11000 13500 16500 19500
Clearance for opening the
inspection doors
mm
700
700
700 /
900*
700
800
900
900
900
900
900
Clearance for changing the
thermal wheel heat exchanger
mm
800
1000
1200
1400
1700
2100
2000
2000
2300
2600
Clearance for air duct
connections above the unit
mm
500
500
600
700
800
900
-
-
-
-
* Unit with boost damper
Содержание CRL evo max Series
Страница 25: ...25 3064361_201811 1 2 3 4 12 Unit splitting for handling purposes CRL ...
Страница 26: ...26 3064361_201811 1 2 3 4 12 Unit splitting for handling purposes CRL ...
Страница 27: ...27 3064361_201811 1 2 3 4 12 Unit splitting for handling purposes CRL ...
Страница 28: ...28 3064361_201811 1 2 3 4 12 Unit splitting for handling purposes CRL ...
Страница 29: ...29 3064361_201811 13 Assembly CRL evo max 4x A1 ...
Страница 30: ...30 3064361_201811 13 Assembly CRL evo max 4x 4x B1 B1 A1 ...
Страница 31: ...31 3064361_201811 13 Assembly CRL evo max ...
Страница 51: ...51 3064361_201811 21 Notes ...
Страница 52: ...WOLF GmbH Postfach 1380 D 84048 Mainburg Tel 49 0 87 51 74 0 Fax 49 0 87 51 74 16 00 www WOLF eu ...