16. Commissioning
CRL-3500 effective pressure
Δp
[Pa] 197
247
301
361
427
498
574
656
744
837
V [m³/h] 1700 1900 2100 2300 2500 2700 2900 3100 3300 3500
The fans used for the CRL-3500 ave a k value of 121.
Ef
fective pressure
Δp [Pa]
Flow rate [m³/h]
Δp = effective pressure
(symbolic representation)
0
200
400
600
800
1000
1500
2000
2500
3000
3500
V
= 121 x √
D
p
w
CRL-4800 effective pressure
The fans used for the CRL-4800 have a k value of 148.
Ef
fective pressure
Δp [Pa]
Flow rate [m³/h]
Δp = effective pressure
(symbolic representation)
0
200
400
600
800
1000
1200
1900
2400
2900
3400
3900
4400
4900
Δp
[Pa] 201
263
333
411
497
592
694
805
924 1052
V [m³/h] 2100 2400 2700 3000 3800 3600 3900 4200 4500 4800
V
= 148 x √
D
p
w