68
3061741_201712.indd
CO
2
adjustment
B) CO
2
adjustment at the lower load - soft start
- Remove the protective screw from the zero point adjusting
screw with a Torx screwdriver.
- Restart the condensing boiler by pressing the "Reset but
-
ton".
- Check and correct (if required) the CO
2
content approx. 20 s
after the burner start with the CO
2
tester, by fine adjusting
the zero point adjusting screw with Torx in accordance with
the table. This adjustment must be made within 180 s after
the burner start. If necessary, press "Reset" to repeat the
start phase for the adjustment.
- During this adjustment, there must be no DHW operation!
- Tighten the protective screw again
- turn clockwise - higher CO
2
content
- turn anti-clockwise - lower CO
2
content
Zero point
adjusting screw
Figure: Gas combination valve
Protective screw
Gas flow
adjusting
screw (only for
natural gas)
D) Completing the adjustments
- Shut down the boiler and close the test ports and hose
connection nipples again. Check the gas supply line and
hydraulics for leaks.
C) Checking the CO
2
adjustment
- After completing the work, refit the casing cover and check
the CO
2
value with the boiler closed
Observe the CO emissions whilst making CO
2
adjustments. The gas combination valve is in-
correctly adjusted if the CO value is > 300 ppm
when the CO
2
value is correct. Take the following
steps:
- Fully insert the zero point adjusting screw
- Open the zero point adjusting screw 1½ revolutions
- Repeat the adjusting process from section A)
- The condensing boiler is correctly adjusted when the CO
2
values correspond to those in the adjacent table
Figure: Flue gas test with a closed boiler
Test port
"Flue gas"
Appliance open
at
lower
load
Natural gas H
8.5% ± 0.2%
LPG P
9.7% ± 0.2%
Appliance closed
at
upper
load
Natural gas H
8.8% ± 0.5%
LPG P
10.3% ± 0.5%
Appliance closed
at
lower
load
Natural gas H
8.7% ± 0.5%
LPG P
9.9% ± 0.5%
Содержание CGB-100
Страница 10: ...Wolf GmbH Postfach 1380 84048 Mainburg Tel 08751 74 0 Fax 08751 741600 Internet www wolf heiztechnik de ...
Страница 20: ...Wolf GmbH Postfach 1380 84048 Mainburg Tel 08751 74 0 Fax 08751 741600 Internet www wolf heiztechnik de ...
Страница 30: ...Wolf GmbH Postfach 1380 84048 Mainburg Tel 08751 74 0 Fax 08751 741600 Internet www wolf heiztechnik de ...
Страница 40: ...Wolf GmbH Postfach 1380 84048 Mainburg Tel 08751 74 0 Fax 08751 741600 Internet www wolf heiztechnik de ...
Страница 50: ...Wolf GmbH Postfach 1380 84048 Mainburg Tel 08751 74 0 Fax 08751 741600 Internet www wolf heiztechnik de ...
Страница 60: ...Wolf GmbH Postfach 1380 84048 Mainburg Tel 08751 74 0 Fax 08751 741600 Internet www wolf heiztechnik de ...
Страница 70: ...Wolf GmbH Postfach 1380 84048 Mainburg Tel 08751 74 0 Fax 08751 741600 Internet www wolf heiztechnik de ...
Страница 80: ...WolfGmbH Postfach1380 D 84048Mainburg Tel 49 8751 74 0 Fax 49 8751 741600 Internet www wolf heiztechnik de ...
Страница 98: ...98 3061741_201712 indd ...
Страница 99: ...99 3061741_201712 indd ...