5
CR185-C60*
CR185-C40*
CR185-C*
35-40Nm
35-40Nm
2x30-35Nm
2x30-35Nm
*Type No. according to
Type No.
Busbar
[mm]
SCCR
[kA]
Voltage/
Current/3pole
(1x) CR185-C40*
30x10
42
1000Vac/Vdc/630A
(1x) CR185-C40*
40x10
42
1000Vac/Vdc/700A
(1x) CR185-C60*
60x10
50
1000Vac/Vdc/1100A
(2x) CR185-C40*
80x10
50
1000Vac/Vdc/1300A
(1x) CR185-C40*
(1x) CR185-C60*
100x10
50
1000Vac/Vdc/1550A
(2x) CR185-C60*
120x10
50
1000Vac/Vdc/1800A
7
Listed accessories for use with Wöhner busbar support only
All devices are suitable for use in branch and feeder circuits
Type No.
Dimension
[mm]
SCCR
[kA]
Voltage/
Current/3pole
30x10-L*
30x10
42
1000Vac/Vdc/630A
40x10-L*
40x10
42
1000Vac/Vdc/700A
60x10-L*
60x10
50
1000Vac/Vdc/1100A
80x10-L*
80x10
50
1000Vac/Vdc/1300A
100x10-L*
100x10
50
1000Vac/Vdc/1550A
120x10-L*
120x10
50
1000Vac/Vdc/1800A
Busbars
Connection Terminals
Type No.
Busbar
[mm]
SCCR
[kA]
Voltage/
Current/3pole
CR185-A2x300*
30x10 - 120x10
35
1000Vac/Vdc/840A
CR185-A80*
30x10 - 40x10
42
1000Vac/Vdc/1400A
60x10 - 120x10
50
CR185-A2x12*
30x10 - 40x10
42
1000Vac/Vdc/1520A
60x10 - 120x10
50
Power Terminals
Listed accessories for use with Wöhner busbar support only
All devices are suitable for use in branch and feeder circuits
CR185-A80*: only for use on a system carrying maximum 1400A
CR185-A2x12*: only for use on a system carrying maximum 1520A
100 mm
Содержание 4021267014308
Страница 11: ......