20
In these examples, the IP address is 192.168.0.1 and the port number is 4000.
You can change these values with the required values.
The APN name, user and password parameters are also required for push mode
operation.
The device will connect to the defined TCP port.
Event Push data format: DLMS WPDU contains the IP address, listening port
number for transparent service, and the meter ID.
TCP data, binary, 29-byte:
0001000100010015FF0203060ACAB60F12232809083035323035383431
Structure:
DLMS WPDU HEADER, 8-byte
Version = 1
srcPort = 1
dstPort = 1
Payload Length = 21
AXDR encoded data packet:
<Data>
<Structure Qty="0003" >
<DoubleLongUnsigned Value="0ACAB60F" /> IP address
<LongUnsigned Value="0FA0" /> port number, that the device listening
on
<OctetString Value="3035323035383431" /> meter ID
</Structure>
</Data>