06
■
Basic Setting
How to Use
Connect Zero Trim Calibrator with the transmitter which is about to calibrate by using a Connecting cable.
buttons, set transmitter pressure range as
By using
Once range is set, by pressing
button, match the measured elctronic current value
with standard current value.
If there is an error, by pressing
button for 5 seconds and repeat for 2~3 times.
Error range of the Standard electronic current value
and measured current value
-15...200 psi
5.116 mA
5.121 mA