6
Wirsbo FlowMaster User Manual
BACKLIGHT 5.0S
CANC OK
➜
➜
Sectio
n
3
—
Setup Menu
3
➜
1/m HARDWARE:
GPM ALL VALVE
LCD CONTRAST 5
CANC OK
➜
➜
The flow-adjustment operation may be necessary in older
radiant floor systems when the water or the sensing ports
of the electronic flow meter nipple darkens due to dirty
water in the system.
The self-calibration requires the electronic flow meter
nipple to remain in a 100% open position (maximum flow)
to obtain an accurate reference point.
On the manifold system, close all valves except the one used for the calibration process.
Attach the probe securely to the electronic flow meter nipple and press [RIGHT] to start the
calibration. The display will return to the previous menu when the calibration is completed.
Press [LEFT] to cancel flow adjustment step.
When the instrument powers off, the FlowMaster returns to the default calibration typically
used in new installations.
To select the appropriate MEASURING UNIT, press the
[UP] or [DOWN] button. Save and quit by pressing
[RIGHT]. To quit without saving, press [LEFT].
This setting remains in memory even if the FlowMaster
powers off, but can be changed any time through the
SETUP menu.
To select the LCD CONTRAST value, press the [UP] or
[DOWN] button. The value range is 1 to 9. Confirm the
setting by pressing [RIGHT], or cancel the value by
pressing [LEFT].
Use the [UP] or [DOWN] button to adjust the BACKLIGHT
duration (idle time). The duration range is 1 to 12.5
seconds. Save the value by pressing [RIGHT], or exit
without saving by pressing [LEFT].
FLOW ADJUST
EXIT START
➜
➜
Flow Adjustment
Measuring Units
LCD Contrast
Backlight
Содержание FlowMaster
Страница 1: ...Wirsbo FlowMaster User Manual...
Страница 4: ...2 Wirsbo FlowMaster User Manual...
Страница 16: ...14 Wirsbo FlowMaster User Manual Notes N...
Страница 17: ...Notes N 15 Wirsbo FlowMaster User Manual...
Страница 18: ...16 Wirsbo FlowMaster User Manual Notes N...
Страница 19: ...Wirsbo FlowMaster Installation Manual...