WirelessHART Fieldgate SWG70
10 Engineering
Hauser
69
Input Register parameters
Parameter
Meaning
Example
Default
Table
Register
Defines the start register for the HART device values
– For Input Register the first value is normally 30000; some
systems work only with Holding Registers starting at 40000
– The intial value can be overwritten only after a device has been
selected in the Long Tag drop-down menu
– Subsequent start registers are automatically generated
13
1
End Register
End register for HART device values (generated automatically)
14
65531
Long Tag
Click to open a drop-down list of connected network devices
–
–
IO-Card
Identifier of fieldgate card used by the device
–
–
Channel
Identifier of card channel used by the device
–
–
Value
Click to open a drop-down list of values for the selected device
–
–
Delete button
Depending upon position, deletes the table or the table line
Generate
Start Register
Defines the start register for the first HART device
– For Input Registers this is normally 1, depending on the Modbus
system in use
13
1
Generation Order
Order in which the devices are mapped to the Modbus registers.
• Index: According to the index number, see Instrument List,
Chapter 10.1, for example
• Alphabetical: In alphabetical order according to the Long Tag
• Alphabetical (sub-device): In alphabetical order according to the
Long Tag of the sub-device.
• IO card & channel: According to the IO card & channel number
of the wireless device.
• IO card & channel (sub-device): According to the IO card &
channel number of the sub-device.
Value
Click to open a drop-down list of values for the selected device
Delete button
Depending upon position, deletes the table or the table line
Default Settings
Adds all HART Command 3 values to the value list, see Appendix A
Generate
Writes mapping table to table in Table tab
Delete all mappings
• Checked: Overwrites any table already in Table tab
• Unchecked: Adds any new devices found to existing table
Controls
Import
Imports a mapping table in CSV format
Export
Exports the current mapping table in CSV format
Refresh
Loads the mapping table currently stored in Fieldgate SWG70
Apply
Stores the current mapping table to Fieldgate SWG70
Содержание Fieldgate SWG70
Страница 2: ......
Страница 118: ...D Appendix ANATEL Approval WirelessHART Fieldgate SWG70 116 Endress Hauser D Appendix ANATEL Approval ...
Страница 119: ...WirelessHART Fieldgate SWG70 D Appendix ANATEL Approval Endress Hauser 117 For your notes ...
Страница 120: ...D Appendix ANATEL Approval WirelessHART Fieldgate SWG70 118 Endress Hauser For your notes ...
Страница 121: ...WirelessHART Fieldgate SWG70 D Appendix ANATEL Approval Endress Hauser 119 For your notes ...
Страница 123: ......
Страница 124: ...www endress com worldwide ...